3.5   Software Sensitivity Tests

This section details the eligibility requirements for an applicant simulation program for use as compliance software under the 2013 Title 24 ACM. A series of quantitative tests called the Software Sensitivity Tests shall be performed to measure the change in energy consumption when changing specified input parameters. Applicant software results will be compared against predetermined Reference results to demonstrate that the applicant software is acceptable for use in code compliance. There are a total of 96 tests. All the test cases described here shall be performed and results summarized in the forms contained in Appendix 3B.

3.5.1.1 Overview

The applicant software shall perform a suite of Software Sensitivity Tests to demonstrate that their performance is acceptable for code compliance.  The applicant software test results shall be compared against a base case called the Reference test case. The Reference Test case is the corresponding match of a particular test case simulated already on EnergyPlus (v.8.1) engine. The Reference test case results, as determined by the Commission, are tabulated in Appendix 3B.

Test cases specific for Simplified geometry are meant for software with 2D inputs for building geometry. Software with 2D geometry approach shall seek certification by submitting the Simplified geometry test cases. In addition, they are also required to produce results for HVAC tests which will be compared against the HAVC reference test results which are performed on detailed geometry.

The test cases will assess the applicant software’s sensitivity to various inputs ranging from envelope thermal conductance to HVAC system performance. Each case tests the impact of the input component on building end use energy and annual TDV. The following six building components will be tested through a series of tests:

•  Opaque envelope

•  Glazing

•  Lighting

•  Daylighting

•  Receptacle loads

•  HVAC System Parameters

3.5.1.2 Prototype Models                                                         

The Software Sensitivity Tests are performed on four Prototype Models which are a subset of the DOE Prototype Building Models developed by PNNL for analysis of ASHRAE Standard 90.1. The Prototype Models are EnergyPlus model input files of the DOE prototype building models, modified to comply with the requirements of Title 24-2013. The Prototype Models will be the reference baseline runs for the test cases. The applicant software shall replicate the four building models using the same inputs as the Prototype Models. The models so replicated will be the applicant baseline models for the test cases.

A summary of the Prototype Models is provided in Appendix 3A Detailed EnergyPlus input files of the Reference baseline models are available from the California Energy Commission’s Building Energy Efficiency Software Consortium webpage http://bees.archenergy.com/

 

Prototype Models used for Software Sensitivity test cases are:

•  Small Office (02000CZ-OffSml):

smOfficeRenderedImage.jpg

The Small Office model is a single story rectangular shaped building of 5500 square feet area. It has punched windows and a hipped roof with Attic space. There are five zones, each served by packaged single zone air conditioner units. For more details refer Appendix 3A This ptoptotype is used for the Simple Geometry test cases only.

•  Medium Office Building (0300CZ-OffMed):

Medium Office

The Medium Office Building model is a three storied rectangular building with an overall area of 53600 square feet. It has a window to wall ratio of 33% with fenestration distributed evenly across all four facades. The zones are served by DX cooling and Gas furnace heating with hot water reheat. For more details refer Appendix 3A. This prototype is used for both Detailed geometry and Simple Geometry test cases.

•  Large Office Building (0400CZ-OffLrg):

 

Large Office

The large office building has twelve floors and a basement floor with glass windows with a window to wall ratio of 40% on the above-grade walls. The total area of the building is 498,600 square feet.  The HVAC system type used VAV system. For more details refer Appendix 3A.

 

•  Stand-Alone Retail  (0500CZ-RetlMed):

 

The stand-alone retail is a single story rectangular building measuring 178 ft by 139 ft. The total area is 24695 square feet. Windows are located only on the street facing façade and occupy 25.4% of that facade. The building is divided into five thermal zones which are served by Packaged Single Zone systems as described in Appendix 3A. This prototype is used for both Detailed geometry and Simple Geometry test cases.

 

•  Strip Mall Building Strip Mall-PSZ System (1000CZ-RetlStrp):

The strip mall building area of 22,500 square feet. It has ten zones each with rooftop units. The building has windows in the street facing façade and has an overall window to wall ratio of 10.5%. For more details refer to Appendix 3A.

 

3.5.1.3 Climate Zones

The Software Sensitivity Test cases use building models for five of the 16 California climate zones. Most tests are performed with two or three climate zones to capture the sensitivity of the input characteristics to extremes in weather conditions. The test cases are performed on climate zones 6, 15 and 16, which represent mild, hot and cold climates respectively. Daylighting tests are performed on climate zone 7, which has a high annual daylighting potential and climate zone 1, representative of the climate with least annual daylighting potential.

 

Table 2-Climate Zones Tested

Climate Zone

Example City / Weather File

1

Arcata /  ARCATA_725945

6

Torrance / TORRANCE_722955

7

San Diego Lindbergh /  SAN-DIEGO-LINDBERGH_722900

15

Palm Springs / PALM-SPRINGS-INTL_722868

16

Blue Canyon / BLUE-CANYON_725845

3.5.1.4 Labeling Test Runs

Each test case in the Software Sensitivity test is labeled uniquely to make it easier to keep track of the runs and to facilitate analysis. The following scheme is used:

XXYYZZ-Prototype-RunDescription

Where,  XX denotes the Prototype Number

YY denotes Test Run Number

ZZ denote Climate zone and

Example:

05 01 15-RetlMed-EnvelopeRoofInsulation                Run Description

                                                                                                       Prototype

                                                                                                       Climate Zone

                                                                                                       Test Run Number

       Prototype Number

 

Example for Simple Geometry Test case

0211015-OffSml-SG-EnvRoofInsulation                                 Run Description

                                                                                                                Prototype

                                                                                                                Climate Zone

                                                                                                                Test Run Number

                                                                                                                Prototype Number

 

3.5.1.5 Test Criteria

Applicant software vendors shall perform a series of computer runs. Each of these runs shall be a systematic variation of the applicant base case model as described in 3.5.1.7. The applicant test case results will be compared to the reference results to verify that applicant software meets the requirements of the ACM. Simulation results for each test case will be compiled in forms provided in Appendix 3B. Compiled results will include annual site energy consumption for each end-use, overall site energy consumption, total unmet load hours and annual TDV and % variation of annual TDV and total end use site energy. 

The annual TDV % variation shall be calculated using the formula:

TDV%= (TDVb – TDVn)/TDVb

Where, TDV% is the TDV % variation,

TDVn is the annual TDV for test case number n and

TDVb is the annual TDV for the base case run.

In order to be accepted, the applicant software should fulfill the passing criteria as determined by the Commission:

When vendor software integrates the CBECC-Com Application Programming Interface (API)

 The change in energy for each test case must be in the same direction as the Reference Method test case result, and must be equal to the Reference Method test case percentage change in TDV energy, plus or minus 0.5% of baseline TDV energy. 

When vendor software does not integrate the CBECC-Com API

Applicant software should fulfill the passing criteria for both the baseline TDV energy comparison and the TDV energy variation tests.

Baseline TDV energy comparison tests:  For each test case, baseline TDV energy results from Applicant Model must be within ±15% of the baseline TDV energy of Reference Method results.

TDV energy comparison tests: For each test case, the change in energy must be in the same direction as the Reference Method test case result, and must be equal to the Reference Method test case percentage change in TDV energy, plus or minus 1% of baseline TDV energy.     

 

Any vendor software meeting these requirements and certified as compliance software under this criteria (not integrating CBECC-Com API) is valid for demonstrating compliance through December 31, 2014. After this date vendor software must integrate CBECC-Com Application Programming Interface (API) and resubmit for certification to the Energy Commission.

3.5.1.6 Reporting Test Results

For each test case, the TDV energy use of the modeled building is reported (kBtu/ft2), along with the TDV energy use attributed to the major fuel types (electricity, gas), site energy use, and energy end use intensity for the regulated end uses (cooling, heating, lighting, etc.).  The following energy totals are reported:

1.   Annual TDV EUI (kBtu/ft2)

2.   Annual Site EUI – Electricity (kWh/ft2) 

3.   Annual SiteEUI – Natural Gas (therm/ft2)

4.   Annual Total End Use Site Energy EUI – kBtu/ft2

 

Site Energy End Uses

5.   Site Energy: Heating (kBtu/ft2)

6.   Site Energy: Cooling (kBtu/ft2)

7.   Site Energy: Interior Lighting (kBtu/ft2)

8.   Site Energy: Interior Equipment (kBtu/ft2)

9.   Site Energy: Fans (kBtu/ft2) (Airside Fans, does not include tower fans)

10.  Site Energy: Pumps (kBtu/ft2)

11.  Site Energy: Towers (kBtu/ft2)Water heating (kBtu/ft2)

12.  TDV % Variation – this field is used for the compliance test

13.  Total End Use Site Energy % - percentage change in site energy use

14.  Pass/Fail – test fails if it does not meet passing criteria

15.  Unmet load hours – these are defined as the zone with the most unmet load hours

a.  Reference Model Occupied Unmet Load Hours

b.  Applicant Model Occupied Unmet Load Hours

c.  Reference Model Number of Zones with excess unmet load hours (>150)

d.  Applicant Model Number of Zones with excess unmet load hours (>150)

 

Figure 3 – Results Spreadsheet Excerpt from Appendix 3B

 

The results spreadsheet provides the results of the Reference Method for each test, and provides a column (in orange) for the vendor to report the results from their candidate compliance software.

The variation from baseline section of the spreadsheet shows the percent change in TDV energy use (kBtu/ft2) from the base case for testing.  The percentage must be within the passing criteria for the candidate software to pass this test.

Also reported is the number of unmet load hours during occupied hours for the building. An unmet load hour for a specific zone in Title 24 compliance is defined as any hour when the zone has an unmet cooling or heating load.  This is typically reported by the software for each zone in the building. For the test case results, two unmet load hour metrics must be reported: the number of unmet load hours for the zone with the greatest number of UMLH, and the number of zones that fail the ACM Reference Manual criteria for acceptable unmet load hours (any zones with greater than 150 hours fail the criteria).

The spreadsheet where the results are documented indicates whether the candidate software passes or fails a test. The result in column AL of the spreadsheet indicates whether or not the candidate software passes the test.

3.5.1.7 Software Sensitivity Test Cases

Test cases assess the energy impact of one or more of the building or system input characteristics on the baseline model. Each test suite consists of a series of unique test cases aimed to test the impact of a specific characteristic on building energy performance. Simulations are grouped according to test criteria and sub-grouped based on the reference model type to allow for direct comparison of results.  For each test case, the applicant software will modify the applicant baseline model with specific inputs as described in the Test Case description section.

The test cases are simulated on multiple California weather files to evaluate the sensitivity of the building or system input to extremes in climate. Results of the test case runs and the TDV percent variation over the baseline run shall be compiled and compared against the reference results.

Detailed descriptions of the Standard Design models are provided in Appendix 3A. CBECC input files for all baseline and test case models are available from the California Energy Commission’s, Building Energy Efficiency Software Consortium webpage http://bees.archenergy.com.  Details on each Test Description can be found in Appendix 3A under the Test Criteria tab.

 

Table 3 – Baseline Runs for Test Cases Test Case Summary

Test Case Name

 

Baseline

Description

050115--RetlMed-EnvelopeRoofInsulation

050015-RetlMed-Baseline

Decrease overall U value of Roof compared to baseline case

050215--RetlMed-EnvelopeWallInsulation

050015-RetlMed-Baseline

Decrease overall U value of Exterior Wall compared to baseline case

050315--RetlMed-EnvelopeHeavy

050015-RetlMed-Baseline

Change Roof and Wall construction assembly to Wood Framed Roof and Heavy Mass wall.

050416--RetlMed-EnvelopeRoofInsulation

050016-RetlMed-Baseline

Decrease overall U value of Roof compared to baseline case

050516--RetlMed-EnvelopeWallInsulation

050016-RetlMed-Baseline

Decrease overall U value of Exterior Wall compared to baseline case

050616--RetlMed-EnvelopeHeavy

050016-RetlMed-Baseline

Change Roof and Wall construction assembly to Wood Framed Roof and Heavy Mass wall.

050706--RetlMed-EnvelopeRoofInsulation

050006-RetlMed-Baseline

Decrease overall U value of Roof compared to baseline case

050806--RetlMed-RetlMed-EnvelopeWallInsulation

050006-RetlMed-Baseline

Decrease overall U value of Exterior Wall compared to baseline case

050906--RetlMed-RetlMed-EnvelopeHeavy

050006-RetlMed-Baseline

Change Roof and Wall construction assembly to Wood Framed Roof and Heavy Mass wall.

031015-OffMed-FloorSlabInsulation

030015-OffMed-Baseline

Change slab F-factor

031215-OffMed-GlazingWindowU

030015-OffMed-Baseline

Decrease SHGC of windows by 20% compared to baseline case

031315-OffMed-GlazingWindowSHGC

030015-OffMed-Baseline

Decrease U value & SHGC of windows by 20% compared to baseline case

031415-OffMed-GlazingWindowUSHGC

030015-OffMed-Baseline

Change Floor slab F factor of permiter zones in the bottom floor to 0.45  0.46

031516-OffMed-FloorSlabInsulation

030016-OffMed-Baseline

Increase Exterior Wall Infiltration by 10% compared to baseline case

031716-OffMed-GlazingWindowU

030016-OffMed-Baseline

Decrease SHGC of windows by 20% compared to baseline case

031816-OffMed-GlazingWindowSHGC

030016-OffMed-Baseline

Decrease U value & SHGC of windows by 20% compared to baseline case

031916-OffMed-GlazingWindowUSHGC

030016-OffMed-Baseline

Change Floor slab F factor of perimeter zones in the bottom floor to 0.45  0.46

032006-OffMed-FloorSlabInsulation

030006-OffMed-Baseline

Increase Exterior Wall Infiltration by 10% compared to baseline case

032206-OffMed-GlazingWindowU

030006-OffMed-Baseline

Decrease SHGC of windows by 20% compared to baseline case

032306-OffMed-GlazingWindowSHGC

030006-OffMed-Baseline

Decrease U value & SHGC of windows by 20% compared to baseline case

032406-OffMed-GlazingWindowUSHGC

030006-OffMed-Baseline

Reduce window area

042507--OffLrg-WWR20%

040007-OffLrg-Baseline

Increase window area

042607--OffLrg-WWR60%

040007-OffLrg-Baseline

 

042801--OffLrg-WWR20%

040001-OffLrg-Baseline

Increase window area

042901--OffLrg-WWR60%

040001-OffLrg-Baseline

Decrease LPD by 20% compared to baseline case

033015-OffMed-LightingLowLPD

030015-OffMed-Baseline

Increase LPD by 20% compared to baseline case

033115-OffMed-LightingHighLPD

030015-OffMed-Baseline

Decrease LPD by 20% compared to baseline case

033216-OffMed-LightingLowLPD

030016-OffMed-Baseline

Increase LPD by 20% compared to baseline case

033316-OffMed-LightingHighLPD

030016-OffMed-Baseline

Decrease LPD by 20% compared to baseline case

033406-OffMed-LightingLowLPD

030006-OffMed-Baseline

Increase LPD by 20% compared to baseline case

033506-OffMed-LightingHighLPD

030006-OffMed-Baseline

Decrease EPD by 20% compared to baseline case

044207--OffLrg-Daylighting Cont.DimHighVT

040007-OffLrg-Baseline

Change daylighting controls in Primary and Secondary daylit areas

044307--OffLrg-Daylighting StepDim

040007-OffLrg-Baseline

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance

044407--OffLrg-Daylighting StepDimHighVT

040007-OffLrg-Baseline

Increase Visible Transmittance of windows compared to baseline case. Reduce window area

044507--OffLrg-Daylighting WWR20Cont.DimHighVT

042507--OffLrg-WWR20%

Change daylighting controls in Primary and Secondary daylit areas. Reduce window area

044607--OffLrg-Daylighting WWR20StepDim

042507--OffLrg-WWR20%

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance of windows. Reduce window area

044707--OffLrg-47CZ07LargeOffice Daylighting WWR20StepDimHighVT

042507--OffLrg-WWR20%

Increase Visible Transmittance compared to baseline case. Increase window area

044807--OffLrg-48CZ07LargeOffice Daylighting WWR60Cont.DimHighVT

042607--OffLrg-WWR60%

Change daylighting controls in Primary and Secondary daylit areas. Increase window area

044907--OffLrg-49CZ07LargeOffice Daylighting WWR60StepDim

042607--OffLrg-WWR60%

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance of windows. Increase window area

045007--OffLrg-50CZ07LargeOffice Daylighting WWR60StepDimHighVT

042607--OffLrg-WWR60%

Increase Visible Transmittance of windows compared to baseline case

045101--OffLrg-51CZ01LargeOffice Daylighting Cont.DimHighVT

040001-OffLrg-Baseline

Change daylighting controls in Primary and Secondary daylit areas

045201--OffLrg-52CZ01LargeOffice Daylighting StepDim

040001-OffLrg-Baseline

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance of windows

045301--OffLrg-53CZ01LargeOffice Daylighting StepDimHighVT

040001-OffLrg-Baseline

Increase Visible Transmittance of windows compared to baseline case. Reduce window area

045401--OffLrg-Daylighting WWR20Cont.DimHighVT

042801--OffLrg-WWR20%

Change daylighting controls in Primary and Secondary daylit areas. Reduce window area

045501--OffLrg-Daylighting WWR20StepDim

042801--OffLrg-WWR20%

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance of windows. Reduce window area

045601--OffLrg-Daylighting WWR20StepDimHighVT

042801--OffLrg-WWR20%

Increase Visible Transmittance of windows compared to baseline case. Increase window area

045701--OffLrg-Daylighting WWR60Cont.DimHighVT

042901--OffLrg-WWR60%

Change daylighting controls in Primary and Secondary daylit areas. Increase window area

045801--OffLrg-Daylighting WWR60StepDim

042901--OffLrg-WWR60%

Change daylighting controls in Primary and Secondary daylit areas and increase visible transmittance of windows. Increase window area

045901--OffLrg-Daylighting WWR60StepDimHighVT

042901--OffLrg-WWR60%

Increase Visible Transmittance of skylights compared to baseline case

056007--RetlMed-Daylighting SRRBaseHighVT

050007-RetlMed-Baseline

Increase skylight area.

056107--RetlMed-Daylighting SRR3.04

050007-RetlMed-Baseline

Increase skylight area and visible transmittance of skylights compared to baseline case.

056207--RetlMed-Daylighting SRR3.04HighVT

050007-RetlMed-Baseline

Increase Visible Transmittance of skylights compared to baseline case

056301--RetlMed-Daylighting SRRBaseHighVT

050001-RetlMed-Baseline

Increase skylight area

056401--RetlMed-Daylighting SRR3.04

050001-RetlMed-Baseline

Increase skylight area and visible transmittance of skylights compared to baseline case

056501--RetlMed-Daylighting SRR3.04HighVT

050001-RetlMed-Baseline

Increase ductloss in the zones served by Pacakaged Single Zone systems.

056616--RetlMed-HVAC DuctLoss

050016-RetlMed-BaselineDuctLoss

 

056716--RetlMed-HVAC DuctLoss

050006-RetlMed-BaselineDuctLoss

Increase ductloss in the zones served by Pacakaged Single Zone systems.

036815-OffMed-HVACPVAV Design

030015-OffMed-Baseline

Change static pressure and motor efficiency of all VAV fans.
See details below

036915-OffMed-HVACPVAV SATControl

030015-OffMed-Baseline

Change supply air temperature reset based on Outside air.
See details below

037015-OffMed-HVACPVAV VAVControl

030015-OffMed-Baseline

Change VAV damper control to dual maximum.

037115-OffMed-HVACPVAV EconomizerType

030015-OffMed-Baseline

Change Economizer Type to Fixed Dry bulb with 70 F high limit

037216-OffMed-HVACPVAV Design

030016-OffMed-Baseline

Change static pressure and motor efficiency of all VAV fans.
See details below

037316-OffMed-HVACPVAV SATControl

030016-OffMed-Baseline

Change supply air temperature reset based on Outside air.
See details below

037416-OffMed-HVACPVAV VAVControl

030016-OffMed-Baseline

Change VAV damper control to dual maximum.

037516-OffMed-HVACPVAV EconomizerType

030016-OffMed-Baseline

Change Economizer Type to Fixed Dry bulb with 70 F high limit

037606-OffMed-HVACPVAV Design

030006-OffMed-Baseline

Change static pressure and motor efficiency of all VAV fans.
See details below

037706-OffMed-HVACPVAV SATControl

030006-OffMed-Baseline

Change supply air temperature reset based on Outside air.
See details below

037806-OffMed-HVACPVAV VAVControl

030006-OffMed-Baseline

Change VAV damper control to dual maximum.

037906-OffMed-HVACPVAV EconomizerType

030006-OffMed-Baseline

Change Economizer Type to Fixed Dry bulb with 70 F high limit

048015--OffLrg-HVACVAV ChillerCOP

040015-OffLrg-Baseline

Increase Chiller COP compared to baseline case

048115--OffLrg-HVACVAV CHWdeltaT

040015-OffLrg-Baseline

Change the Chilled water loop design temperature difference

048215--OffLrg-HVACVAV CWSetpoint

040015-OffLrg-Baseline

Change condenser water setpoint reset  based on Outdoor air wet bulb temperature

048315--OffLrg-HVACVAV TowerEff

040015-OffLrg-Baseline

Change Tower Efficiency

048416--OffLrg-HVACVAV ChillerCOP

040016-OffLrg-Baseline

Increase Chiller COP

048516--OffLrg-HVACVAV CHWdeltaT

040016-OffLrg-Baseline

Change the Chilled water loop design temperature difference

048616--OffLrg-HVACVAV CWSetpoint

040016-OffLrg-Baseline

Change condenser water setpoint reset  based on Outdoor air wet bulb temperature

048706--OffLrg-HVACVAV TowerEff

040016-OffLrg-Baseline

Change Tower Efficiency

048806--OffLrg-HVACVAV ChillerCOP

040006-OffLrg-Baseline

Increase Chiller COP

048906--OffLrg-HVACVAV CHWdeltaT

040006-OffLrg-Baseline

Change the Chilled water loop design temperature difference

049006--OffLrg-HVACVAV CWSetpoint

040006-OffLrg-Baseline

Change condenser water setpoint reset  based on Outdoor air wet bulb temperature

049106--OffLrg-HVACVAV TowerEff

040006-OffLrg-Baseline

Change condenser water setpoint reset  based on Outdoor air wet bulb temperature

109215--RetlStrp-HVACPSZ DXCOP

100015-RetlStrp-BaselinePSZ

Increase COP of  DX coil

109315--RetlStrp-HVACPSZ HeatEff

100015-RetlStrp-BaselinePSZ

Increase  efficiency of the Heating coil

109415--RetlStrp-HVACPSZ EconomizerControl

100015-RetlStrp-BaselinePSZ

Change Economizer from Integrated as in baseline to NonIntegrated.

109516--RetlStrp-HVACPSZ DXCOP

100016-RetlStrp-BaselinePSZ

Increase COP of  DX coil

109616--RetlStrp-HVACPSZ HeatEff

100016-RetlStrp-BaselinePSZ

Increase  efficiency of the Heating coil

109716--RetlStrp-HVACPSZ EconomizerControl

100016-RetlStrp-BaselinePSZ

Change Economizer from Integrated as in baseline to NonIntegrated.

109806--RetlStrp-HVACPSZ DXCOP

100006-RetlStrp-BaselinePSZ

Increase COP of  DX coil

109906--RetlStrp-HVACPSZ HeatEff

100006-RetlStrp-BaselinePSZ

Increase efficiency of the Heating coil

1010006--RetlStrp-HVACPSZ EconomizerControl

100006-RetlStrp-BaselinePSZ

Change Economizer from Integrated as in baseline to NonIntegrated.

1010115--RetlStrp-HVACPTAC DXCOP

100015-RetlStrp-BaselinePTAC

Increase COP of  DX coil

1010215--RetlStrp-HVACPTAC DXCOP

100016-RetlStrp-BaselinePTAC

Increase COP of  DX coil

1010315--RetlStrp-HVACPTAC DXCOP

100006-RetlStrp-BaselinePTAC

Increase COP of  DX coil

1010415--RetlStrp-HVACPTAC vsFanCoil

100015-RetlStrp-BaselinePTAC

Comparison of PTAC system with Fan Coil system

1010516--RetlStrp-HVACPTAC vsFanCoil

100016-RetlStrp-BaselinePTAC

Comparison of PTAC system with Fan Coil system

1010606--RetlStrp-HVACPTAC vsFanCoil

100006-RetlStrp-BaselinePTAC

Comparison of PTAC system with Fan Coil system

0211015-OffSml-SG-EnvRoofInsulation            

0200015-OffSml-SG-Baserun

Decrease overall U value of Roof by 20% compared to baserun case       

0211116-OffSml-SG-EnvRoofInsulation            

0200016-OffSml-SG-Baserun

Decrease overall U value of Roof by 20% compared to baserun case       

0211206-OffSml-SG-EnvRoofInsulation            

0200006-OffSml-SG-Baserun

Decrease overall U value of Roof by 20% compared to baserun case       

0211315-OffSml-SG-EnvWallInsulation             

0200015-OffSml-SG-Baserun

Decrease overall U value of Exterior Wall by 20% compared to baseline case               

0211416-OffSml-SG-EnvWallInsulation             

0200016-OffSml-SG-Baserun

Decrease overall U value of Exterior Wall by 20% compared to baseline case               

0211506-OffSml-SG-EnvWallInsulation

0200006-OffSml-SG-Baserun

Decrease overall U value of Exterior Wall by 20% compared to baseline case

0311615-OffMed-SG-WWR40             

0300015-OffMed-SG-Baseline

Change WWR from 33% to 40%

0311715-OffMed-SG-WWR20             

0300015-OffMed-SG-Baseline

Change WWR from 33% to 20%

0311816-OffMed-SG-WWR40             

0300016-OffMed-SG-Baseline

Change WWR from 33% to 40%

0311916-OffMed-SG-WWR20             

0300016-OffMed-SG-Baseline

Change WWR from 33% to 20%

0312006-OffMed-SG-WWR40             

0300006-OffMed-SG-Baseline

Change WWR from 33% to 40%

0312106-OffMed-SG-WWR20             

0300006-OffMed-SG-Baseline

Change WWR from 33% to 20%

0312215-OffMed-SG-WinUSHGC       

0300015-OffMed-SG-Baseline

Decrease U value of windows by 20% compared to baseline case

0312316-OffMed-SG-WinUSHGC       

0300016-OffMed-SG-Baseline

Decrease SHGC of windows by 20% compared to baseline case

0312406-OffMed-SG-WinUSHGC

0300006-OffMed-SG-Baseline

Decrease U value & SHGC of windows by 20% compared to baseline case

0511615RetlMed-SG-SRR5 

050015RetlMed-SG-Baseline

Change SRR to 5%     

0511716RetlMed-SG-SRR5 

050016RetlMed-SG-Baseline

Change SRR to 5%     

0511806RetlMed-SG-SRR5 

050006RetlMed-SG-Baseline

Change SRR to 5%     

0511915RetlMed-SG-SRR1 

050015RetlMed-SG-Baseline

Change SRR to 1%     

0512016RetlMed-SG-SRR1 

050016RetlMed-SG-Baseline

Change SRR to 1%     

0512106RetlMed-SG-SRR1 

050006RetlMed-SG-Baseline

Change SRR to 1%     

0512215RetlMed-SG-SkyUSHGC       

050015RetlMed-SG-Baseline

Decrease U value of skylights by 20% compared to baseline case       

0512316RetlMed-SG-SkyUSHGC       

050016RetlMed-SG-Baseline

Decrease U value of skylights by 20% compared to baseline case       

0512406RetlMed-SG-SkyUSHGC

050006RetlMed-SG-Baseline

Decrease U value of skylights by 20% compared to baseline case

 

3.5.1.8 Results Documentation

The applicant shall perform simulations for all tests specified above. Detailed description of each test case is provided in Appendix 3A and report results in the forms provided in Appendix 3B. Some of the prototype models have some variants of the baseline model. These include 1) Stand Alone Duct Loss baseline- a variant of the Stand-Alone Retail model 2) StripMall-PTAC model- a variant of StripMall- PSZ model and 3) StripMall- Fan Coil model- a variant of StripMall PSZ model. For details please refer Appendix 3A.

 

A test case is presented here as an example: one for building envelope, one for lighting and daylighting, and one for HVAC. The development of the other required test cases follows the same process.

 

Example Test Case: 19CZ16MediumOfficeGlazingWindowUSHGC

For this test case the U-factor and SHGC of all vertical fenestration is decreased by 20%. The prototype used for this test case is a medium office building.

Before the test cases are run, the first step is to generate the prototype models for the four reference buildings, which are required for all of the tests.  The four prototype models are defined in the PrototypeModel spreadsheet of Appendix 3A. (Note: while many of the prototype model inputs are based on Title 24 prescriptive requirements, the prototype models do not exactly conform to minimum Title 24 requirements, but rather, are intended to test the sensitivity of the candidate software simulation results to common variations in building inputs

Step 1. Generate prototype models. The first step is to generate the prototype building for the medium office building.  The detailed specification of the medium office building is 'listed in Appendix 3A.  A portion of the inputs are shown in the Figure below.  The prototypes are defined for the reference models on the Prototype Model tab of Appendix 3A. 

Figure 4 – Prototype Model Definition from Appendix 3A

 

The prototype model definition in the spreadsheet contains links to other input definitions:

Row 19, 26,45: Links to layer-by-layer exterior construction assembly definitions in the ConstructionAssembly tab

Row 52: links to layer-by-layer interior construction assembly definitions in the ConstructionAssembly tab

Row 85, 105, 107, 109, 112: links to fan and equipment hourly schedules in the Schedules tab

Row 112, 116, 119: links to space use interior load schedules in the Schedules tab

 

Step 2. Define base case and variation for test run.

The base case is defined as the starting point for each test. In many tests, the base case will be one of the prototype models. However, in some cases, a variation of the prototype may serve as the base case for the test.

For this test, the base case is found by looking at the Test Criteria spreadsheet:

Figure 5 – Base Case Definition from Appendix 3A

 

For this test, the Baseline field in row 3 of the TestCriteria tab shows that the baseline is CZ06MediumOffice, the medium office prototype in climate zone 6.

This same TestCriteria tab shows the input(s) to be verified, which are highlighted in purple. For this test, the solar heat gain coefficient of all vertical fenestration is reduced by 20%, from 0.25 to 0.20.

Figure 6 – Input Parameter Variation for Medium Office from Appendix 3A

 

Step 3. Run the base case model and generate test results.

Once the base case model is developed, the simulation is run and the results are recorded onto the spreadsheet of test cases, Appendix 3B.

The candidate software shall report electricity use by end use, gas use by end use, TDV energy and unmet load hours. For purposes of compliance, unmet load hours are defined at the zone level, and the zone with the greatest number of unmet load hours must pass the criteria specified in the sizing procedure.

 

For the Reference Tests, the HVAC system’s capacities and flow rates can be found in Appendix 3A under the Sizing Values tab.:

 

Step 4. Run the test case model (with the reduced solar heat gain coefficient) and report the results.

The model is re-run and the energy results and outputs are reported. The percentage change in energy use is reported.

 

Step 5. Report the change in regulated TDV energy use from the base case as a percentage change.

The reported percentage change in energy use from the candidate compliance software must fall within the passing criteria for the Reference Method.