SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROL DEVICES AND SYSTEMS, BALLASTS, AND LUMINAIRES

          

(a)  All lighting control devices and systems, ballasts, and luminaires...

... subject to the requirements of Section 110.9 shall meet the following requirements:

1.   Shall be installed only if the lighting control device or system, ballast, or luminaire complies with all of the applicable requirements of Section 110.9.

2.   Lighting controls may be individual devices (Self Contained Lighting Control) or systems (Lighting Control Systems) consisting of two or more components.

3.   Self Contained Lighting Controls, as defined in Section 100.1, shall be certified by the Manufacturer as required by the Title 20 Appliance Efficiency Regulations.

4.   Lighting Control Systems, as defined in Section 100.1, shall be a fully functional lighting control system complying with the applicable requirements in Section 110.9(b), and shall meet the Lighting Control Installation requirements in Section 130.4.

5.   If indicator lights are integral to a lighting control system, they shall consume no more than one watt of power per indicator light.

(b) All Installed Lighting Control Systems…

…'listed in Section 110.9(b) shall comply with the requirements 'listed below; and all components of the system considered together as installed shall meet all applicable requirements for the application for which they are installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0, and Section 150.0(k).

1.   Time-Switch Lighting Controls

A.   'Automatic Time-Switch Controls shall meet all requirements for Automatic Time Switch Control devices in the Title 20 Appliance Efficiency Regulations.

B.   Astronomical Time-Switch Controls shall meet all requirements for Astronomical Time-Switch Control devices in the Title 20 Appliance Efficiency Regulations.

C.   Multi-Level Astronomical Time-Switch Controls, in 'addition to meeting all of the requirements for Astronomical Time-Switch Controls, shall include at least 2 separately programmable steps per zone.

D.   Outdoor Astronomical Time-Switch Controls, in 'addition to meeting all of the requirements for Astronomical Time-Switch Controls, shall have setback functions that allow the lighting on each controlled channel to be switched or dimmed to lower levels. The set back functions shall be capable of being programmed by the user for at least one specific time of day.

2.   Daylighting Controls   

A.   Automatic Daylight Controls shall meet all requirements for Automatic Daylight Control devices in the Title 20 Appliance Efficiency Regulations.

B.   Photo Controls shall meet all requirements for Photo Control devices in the Title 20 Appliance Efficiency Regulations.

3.   Dimmers shall meet all requirements for Dimmer Control devices in the Title 20 Appliance Efficiency Regulations.

4.   'Occupant Sensing Controls: Occupant, Motion, and Vacancy Sensor Controls shall meet the following requirements:

A.   Occupant Sensors shall meet all applicable requirements for Occupant Sensor Control devices in the Title 20 Appliance Efficiency Regulations.

B.   Motion Sensors shall meet all applicable requirements for Motion Sensor Controls devices in the Title 20 Appliance Efficiency Regulations.

C.   Vacancy Sensors shall meet all applicable requirements for Vacancy Sensor Controls devices in the Title 20 Appliance Efficiency Regulations.

D.   Partial-ON Sensors shall meet all applicable requirements for partial on sensing devices in the Title 20 Appliance Efficiency Regulations.

E.   Partial-OFF Sensors shall meet all applicable requirements for partial off sensing devices in the Title 20 Appliance Efficiency Regulations.

EXCEPTION to Section 110.9(b)4:  Occupant Sensing Control systems may consist of a combination of single or multi-level Occupant, Motion, or Vacancy Sensor Controls, provided that components installed to comply with manual-on requirements shall not be capable of conversion by the user from manual-on to automatic-on functionality.

5.   Part-Night 'Outdoor Lighting Controls, as defined in Section 100.1, shall meet all of the following requirements:

A.   Have sunrise and sunset prediction accuracy within +/- 15 minutes and timekeeping accuracy within five minutes per year; and

B.   Have the ability to setback or turn off lighting at night as required in Section 130.2(c), by means of a programmable timeclock or motion sensing device; and

C.   When controlled with a timeclock, shall be capable of being programmed to allow the setback or turning off of the lighting to occur from any time at night until any time in the morning, as determined by the user.

(c)  Track Lighting Integral Current Limiter.

An integral current limiter for line-voltage track lighting shall be recognized for compliance with Part 6 only if it meets all of the following requirements:

1.   Shall be certified to the Energy Commission as meeting all of the applicable requirements in Section 110.9(c); and

2.   Shall comply with the Lighting Control Installation requirements in accordance with Section 130.4; and

3.   Shall be manufactured so that the current limiter housing is used exclusively on the same manufacturer's track for which it is designed; and

4.   Shall be designed so that the current limiter housing is permanently attached to the track so that the system will be irreparably damaged if the current limiter housing were to be removed after installation into the track. Methods of attachment may include but are not limited to one-way barbs, rivets, and one-way screws; and

5.   Shall employ tamper resistant fasteners for the cover to the wiring compartment; and

6.   Shall have the identical volt-ampere (VA) rating of the current limiter, as installed and rated for compliance with Part 6 clearly marked as follows; and:

A.   So that it is visible for the building officials’ field inspection without opening coverplates, fixtures, or panels; and

B.   Permanently marked on the circuit breaker; and

C.   On a factory-printed label that is permanently affixed to a non-removable base-plate inside the wiring compartment.

7.   Shall have a conspicuous factory installed label permanently affixed to the inside of the wiring compartment warning against removing, tampering with, rewiring, or bypassing the device; and

8.   Each electrical panel from which track lighting integral current limiters are energized shall have a factory printed label permanently affixed and prominently located, stating the following: "NOTICE: Current limiting devices installed in track lighting integral current limiters connected to this panel shall only be replaced with the same or lower amperage. Adding track or replacement of existing current limiters with higher continuous ampere rating will void the track lighting integral current limiter certification, and will require re-submittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.”

(d) Track Lighting Supplementary Overcurrent Protection Panel.  

A Track Lighting Supplementary Overcurrent Protection Panel shall be used only for line-voltage track lighting and shall be recognized for compliance with Part 6 only if it meets all of the following requirements:

1.   Shall comply with the Lighting Control Installation requirements in accordance with Section 130.4; and

2.   Shall be 'listed as defined in Section 100.1; and

3.   Shall be used only for line voltage track lighting. No other lighting or building power shall be used in a Supplementary Overcurrent Protection Panel used to determine input wattage for track lighting; and

4.   Be permanently installed in an electrical equipment room, or permanently installed adjacent to the lighting panel board providing supplementary overcurrent protection for the track lighting circuits served by the supplementary over current protection pane; and

5.   Shall have a permanently installed label that is prominently located stating the following: "NOTICE: This Panel for Track Lighting Energy Code Compliance Only. The overcurrent protection devices in this panel shall only be replaced with the same or lower amperage. No other overcurrent protective device shall be added to this panel. Adding to, or replacement of existing overcurrent protective device(s) with higher continuous ampere rating, will void the panel listing and require re-submittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.”

(e)  Residential High Efficacy Light Emitting Diode (LED) Lighting.     

To qualify as high efficacy for compliance with the residential lighting Standards in Section 150.0(k), a residential LED luminaire or LED light engine shall be certified to the Energy Commission according to Reference Joint Appendix JA8. LED lighting not certified to the Energy Commission shall be classified as low efficacy for compliance with Section 150.0(k). Nonresidential LED lighting is not required to be certified to the Energy Commission.

(f)  Ballasts for Residential Recessed Luminaires.

To qualify as high efficacy for compliance with Section 150.0(k), any compact fluorescent lamp ballast in a residential recessed luminaire shall meet all of the following conditions:

1.   Be rated by the ballast manufacturer to have a minimum rated life of 30,000 hours when operated at or below a specified maximum case temperature. This maximum ballast case temperature specified by the ballast manufacturer shall not be exceeded when tested in accordance to UL 1598 Section 19.15; and

2.   Have a ballast factor of not less than 0.90 for non-dimming ballasts and a ballast factor of not less than 0.85 for dimming ballasts.