10.5 Commercial Refrigeration

10.5.1  Overview

This section of the nonresidential compliance manual addresses Section §120.6(b) of the Standards – mandatory requirements for commercial refrigeration systems in retail food stores.  The chapter includes mandatory requirements for condensers, compressor systems, refrigerated display cases, refrigeration heat recovery.  All buildings under Part 6 of Title 24 must also comply with the General Provisions of the Standards (§100.0 – §100.2, §110.0 – §110.10, §120.0 – §120.9, §130.0 – §130.5), and additions and alterations requirements (§141.1).

A.   Organization and Content

This section of the manual focuses on the Standards provisions unique to commercial refrigeration.  This chapter is organized as follows:

•   Section 10.5.1            Overview

•      Section 10.5.2   Condensers Mandatory Requirements §120.6(b)1

•      Section 10.5.3   Compressor System Mandatory Requirements §120.6(b)2

•      Section 10.5.4   Refrigerated Display Case Mandatory Requirements §120.6(b)3

•      Section 10.5.5   Refrigeration Heat Recovery Mandatory Requirements §120.6(b)4

•      Section 10.5.6 Additions and Alterations §141.1

•      Section 10.5.7 Compliance Documentation

B.   Mandatory Measures and Compliance Approaches

The energy efficiency requirements for commercial refrigeration are all mandatory.  There are no prescriptive requirements or performance compliance paths for commercial refrigeration.  Since the provisions are all mandatory, there are no tradeoffs allowed between the various requirements.  The application must demonstrate compliance with each of the mandatory measures.  Exceptions to each mandatory requirement where provided are described in each of the mandatory measure sections below.

C.   Scope and Application

Commercial refrigeration requirements (§120.6(b)) were not a part of the 2008 Standards. Therefore, all the requirements related to commercial refrigeration in the 2013 Standards are new.

§120.6(b) of the Standards applies to retail food stores that have 8,000 square feet or more of conditioned area, and utilize either refrigerated display cases or walk-in coolers or freezers, which are connected to remote compressor units or condensing units.  The Standards have minimum requirements for the condensers, compressor systems, refrigerated display cases, and refrigeration heat recovery systems associated with the refrigeration systems in these facilities.

The Standards do not have minimum efficiency requirements for walk-ins, as these are deemed appliances and are covered by the California Appliance Efficiency Regulations (Title 20) and Federal Energy Independence and Security Act of 2007.  Walk-ins are defined as refrigerated spaces with less than 3,000 square feet of floor area that are designed to operate below 55°F (13°C).  Additionally, the Standards do not have minimum equipment efficiency requirements for refrigerated display cases, as the minimum efficiency for these units is established by Federal law in the Commercial Refrigeration Equipment Final Rule but there are requirements for display cases that do result in reduced energy consumption.

Example 10-9

Question

The only refrigeration equipment in a retail food store with 10,000 square feet of conditioned area is self-contained refrigerated display cases.  Does this store need to comply with the requirements for Commercial Refrigeration?

Answer

No.  Since the refrigerated display cases are not connected to remote compressor units or condensing units, the store does not need to comply with the Standards.

 

Example 10-10

Question

A new retail store with 25,000 square feet conditioned area has two self-contained display cases. The store also has several display case line-ups and walk-in boxes connected to remote compressors systems.  Do all the refrigeration systems need to comply with the requirements for Commercial Refrigeration?

Answer

There are no provisions in the Standards for the two self-contained display cases.  The refrigeration systems serving the other fixtures must comply with the Standards.

10.5.2  Condensers Mandatory Requirements

Subsection 1 of the commercial refrigeration section addresses the mandatory requirements for condensers serving commercial refrigeration systems.  These requirements only apply to stand-alone refrigeration condensers and do not apply to condensers that are part of a unitary condensing unit.

If the work includes a new condenser replacing an existing condenser, the condenser requirements do not apply if all of the following conditions apply:

1.   The Total Heat of Rejection of the compressor system attached to the condenser or condenser system does not increase, and

2.   Less than 25% of the attached refrigeration system compressors (based on compressor capacity at design conditions) are new, and

3.   Less than 25% of the display cases (based on display case design load at applied conditions) that the condenser serves, are new.  Since the compressor system loads commonly include walk-ins (both for storage and point-of-sale boxes with doors), the 25% “display case" should be calculated with walk-ins included.

Example 10-11

Question

A supermarket remodel includes a refrigeration system modification where some of the compressors will be replaced, some of the refrigerated display cases will be replaced, and the existing condenser will be replaced.  The project does not include any new load and the design engineer has determined that the total system heat of rejection will not increase.  The replacement compressors comprise 20% of the suction group capacity at design conditions, and the replacement display cases comprise 20% of the portion of the design load that comes from display cases.  There are no changes in walk-ins.  Does the condenser have to comply with the provisions of the Standards?

Answer

No.  This project meets all three criteria of the exception to the mandatory requirements for condensers:

1.  The new condenser is replacing an existing condenser

2.  The total heat of rejection of the subject refrigeration system does not increase

3a. The replacement compressors comprise less than 25% of the suction group design capacity at design conditions

3b. The replacement display cases comprise less than 25% of the portion of the design load that comes from display cases.

A.   Condenser Fan Control

Condenser fans for new air-cooled or evaporative condensers, or fans on air- or water-cooled fluid coolers or cooling towers used to reject heat on new refrigeration systems, must be continuously variable speed.  Variable frequency drives are commonly used to provide continuously variable speed control of condenser fans and controllers designed to vary the speed of electronically commutated motors are increasingly being used for the same purpose.  All fans serving a common high side, or indirect condenser water loop, shall be controlled in unison.  Thus, in normal operation, the fan speed of all fans within a single condenser or set of condensers serving a common high-side should modulate together, rather than running fans at different speeds or staging fans off.  However, when fan speed is at the minimum practical level minimum level, usually no higher than 10-20%, the fans may be staged off to further reduce condenser capacity.  As load increases, fans should be turned back on prior to significantly increasing fan speed, recognizing a control band is necessary to avoid without excessive fan cycling.  Control of air-cooled condensers may also keep fans running and use a holdback valve on the condenser outlet to maintain the minimum condensing temperature once all fans have reached minimum speed; with the holdback valve set below the fan control minimum saturated condensing temperature setpoint.

To minimize overall system energy consumption, the condensing temperature control setpoint must be continuously reset in response to ambient temperatures, rather than using a fixed setpoint value.  This strategy is also termed ambient-following control, ambient-reset, wetbulb following and drybulb following—all referring to control logic which changes the condensing temperature control setpoint in response to ambient conditions at the condenser.  The control system calculates a control setpoint saturated condensing temperature that is higher than the ambient temperature by a predetermined temperature difference (i.e. the condenser control TD).  Fan speed is then modulated so that the measured SCT (saturated condensing temperature) matches the calculated SCT control setpoint.  The SCT control setpoint  for evaporative condensers or water-cooled condensers (via cooling towers or fluid coolers) must be reset according to ambient wet bulb temperature, and the SCT control setpoint for air-cooled condensers must be reset according to ambient dry bulb temperature.

The condenser control TD is not specified in the Standard.  The nominal control value is often equal to the condenser design TD; however the value for a particular system is left up to the system designer.  Since the intent is to utilize as much condenser capacity as possible without excessive fan power, common practice is to optimize the control TD over a period of time such that the fan speed is in a range of approximately 60-80% during normal operation (i.e. when not at minimum SCT and not in heat recovery).

The minimum saturated condensing temperature setpoint must be 70°F (21°C) or less.  For systems utilizing halocarbon refrigerants with glide, the SCT setpoint shall correlate with a midpoint temperature (between the refrigerant bubble-point and dew point temperatures) of 70°F (21°C) or less.  As a practical matter, a maximum SCT setpoint is also commonly employed to set an upper bound on the control setpoint in the event of a sensor failure and to force full condenser operation during peak ambient conditions.  This value should be set high enough that it does not interfere with normal operation.

Split air-cooled condensers are sometimes used for separate refrigeration systems, with two circuits and two rows of condenser fans.  Each condenser half would be controlled as a separate condenser.  If a condenser has multiple circuits served by a common fan or set of fans, the control strategy may utilize the average condensing temperature or the highest condensing temperature of the individual circuits as the control variable for controlling fan speed.

Alternative control strategies are permitted to the condensing temperature reset control required in Section §120.6(b)1C.  The alternative control strategy must be demonstrated to provide equal or better performance, as approved by the Executive Director.

Hybrid condensers, manufactured with integral capability to operate with either air-cooled or evaporative-cooled operation, are not covered.  Air-cooled condensers with separately installed evaporative precoolers added to the condenser are not considered hybrid condensers for the purpose of this Standard.  Air cooled condensers with an added evaporative precooling must meet the requirements for air cooled equipment, including specific efficiency and ambient-following control.

 

Example 10-12

Question

A new supermarket with an evaporative condenser is being commissioned.  The control system designer has utilized a wet bulb-following control strategy to reset the system saturated condensing temperature (SCT) setpoint.  The refrigeration engineer has calculated that adding a TD of 15°F (8.3°C) above the ambient wet bulb temperature should provide a saturated condensing temperature setpoint that minimizes the combined compressor and condenser fan power usage throughout the year.  What might the system SCT and SCT setpoint trends look like over an example day?

Answer

The following figure illustrates what the actual saturated condensing temperature and SCT setpoints could be over an example day using the wet bulb-following control strategy with a 15°F (8.3°C) TD and also observing the 70°F (21°C) minimum condensing temperature requirement.  As the figure shows, the SCT setpoint is continuously reset to 15°F (8.3°C) above the ambient wet bulb temperature until the minimum SCT setpoint of 70°F is reached. The figure also shows a maximum SCT setpoint (in this example, 90°F (32.2°C) which may be utilized to limit the maximum control setpoint, regardless of the ambient temperature value or TD parameter.

B.   Condenser Specific Efficiency

All newly installed evaporative condensers and air-cooled condensers with capacities greater than 150,000 Btuh (at the specific efficiency rating conditions) shall meet the minimum specific efficiency requirements shown in Table 10-2.

Table 10-2 – Fan-powered Condensers – Minimum Specific Efficiency Requirements

Condenser Type

Minimum Specific Efficiency

Rating Condition

Evaporative-Cooled

160 Btuh/Watt

100°F Saturated Condensing Temperature (SCT),

70°F Entering Wetbulb Temperature

Air-Cooled

65 Btuh/Watt

105°F Saturated Condensing Temperature (SCT),

95°F Entering Drybulb Temperature

Condenser specific efficiency is defined as:

Condenser Specific Efficiency = Total Heat Rejection (THR) Capacity / Input Power

The total heat rejection capacity is defined at the rating conditions of 100°F Saturated Condensing Temperature (SCT) and 70°F outdoor wetbulb temperature for evaporative condensers, and 105°F SCT and 95°F outdoor drybulb temperature for air-cooled condensers.  Input power is the electric input power draw of the condenser fan motors (at full speed), plus the electric input power of the spray pumps for evaporative condensers.  The motor power is the manufacturer’s published applied power for the subject equipment, which is not necessarily equal to the motor nameplate rating.  Power input for secondary devices such as sump heaters shall not be included in the specific efficiency calculation.

The data published in the condenser manufacturer’s published rating for capacity and power shall be used to calculate specific efficiency.  For evaporative condensers, manufacturers typically provide nominal condenser capacity, and tables of correction factors that are used to convert the nominal condenser capacity to the capacity at various applied condensing temperatures and wetbulb temperatures.  Usually the manufacturer publishes two sets of correction factors: one is a set of “heat rejection” capacity factors, while the others are “evaporator ton” capacity factors.  Only the “heat rejection” capacity factors shall be used to calculate the condenser capacity at the efficiency rating conditions for the purpose of determining compliance with this section.

For air-cooled condensers, manufacturers typically provide the capacity at a given temperature difference (TD) between SCT and drybulb temperature.  Manufacturers typically assume that air-cooled condenser capacity is linearly proportional to TD; the catalog capacity at 20°F TD is typically twice as much as at 10°F TD.  The condenser capacity for air-cooled condensers at a TD of 10°F shall be used to calculate efficiency.  If the capacity at 10°F TD is not provided, the capacity shall be scaled linearly.

Depending on the type of condenser, the actual manufacturer’s rated motor power may vary from motor nameplate in different ways.  Air cooled condensers with direct-drive OEM motors may use far greater input power than the nominal motor horsepower would indicate.  On the other hand, evaporative condenser fans may have a degree of safety factor to allow for higher motor load in cold weather conditions (vs. the 100°F SCT/70°F WBT specific efficiency rating conditions).  Thus, actual motor input power from the manufacturer must be used for direct-drive air-cooled condensers.  For evaporative condensers and fluid coolers, the full load motor power, using the minimum allowable motor efficiencies published in the Nonresidential Appendix NA3: Fan Motor Efficiencies, is generally conservative but manufacturer’s applied power should be used whenever possible to more accurately determine specific efficiency.

There are three exceptions to the condenser specific efficiency requirements.

1.   If the store is located in Climate Zone 1 (the cool coastal region in northern California), or

2.   If an existing condenser is reused for an addition of alteration, or

3.   If the condenser capacity is less than 150 MBH at the specific efficiency rating conditions

Example 10-13

Question

An air-cooled condenser is being designed for a new supermarket.  The refrigerant is R-507.  The condenser manufacturer’s catalogue states that the subject condenser has a capacity of 500 MBH at 10°F TD between entering air and saturated condensing temperatures with R-507 refrigerant.  Elsewhere in the catalog, it states that the condenser has ten ½ hp fan motors that draw 450 Watts each.  Does this condenser meet the minimum efficiency requirements?

Answer

First, the condenser capacity must be calculated at the specific efficiency rating condition.  From Table 10-6, we see that the rating conditions for an air-cooled condenser are 95°F entering drybulb temperature and 105°F SCT.  The catalog capacity is at a 10°F temperature difference, which is deemed suitable for calculating the specific efficiency (105°F SCT - 95°F entering Drybulb = 10°F TD).  Input power is equal to the number of motors multiplied by the input power per motor:

10 fan motors x 450 Watts = 4,500 Watts
                        fan motor

The specific efficiency of the condenser is therefore:

500MBH x 1,000 Btu/hr / 4,500Watts = 111Btu/hr/ Watts
                        4,500 Watts

                       

This condenser has a specific efficiency of 111 Btuh per Watt, which is higher than the 65 Btuh per Watt minimum requirement.  This condenser meets the minimum specific efficiency requirements.

Example 10-14

Question

An evaporative condenser is being designed for a new supermarket.  The manufacturer’s catalog provides a capacity of 2,000 MBH at standard conditions of 105°F SCT and 78°F wetbulb temperature.  The condenser manufacturer’s catalog provides the following heat rejection capacity factors:

Elsewhere in the catalog, it states that the condenser model has one 10 HP fan motor and one 2 HP pump motor.  Fan motor efficiencies and motor loading factors are not provided by the manufacturer.  Does this condenser meet the minimum efficiency requirements?

Answer

First, the condenser capacity must be calculated at the specific efficiency rating condition.  From Table 10-6, we see that the rating conditions for an evaporative condenser are 100°F SCT, 70°F WBT and a minimum specific efficiency requirement is 160 Btuh/Watt.  From the Heat Rejection Capacity Factors table, we see that the correction factor at 100°F SCT and 70°F WBT is 0.95.  The capacity of this model at the specific efficiency rating conditions is:

 

2,000 MBH / 0.95 = 2,105 MBH

To calculate input power, we will assume 100% fan and pump motor loading and minimum motor efficiencies since the manufacturer has not yet published actual motor specific efficiency at the specific efficiency rating conditions.  We look up the minimum motor efficiency from Nonresidential Appendix NA3: Fan Motor Efficiencies.  For a 10 HP 6-pole open fan motor, the minimum efficiency is 91.7%.  For a 2 HP 6-pole open pump motor, the minimum efficiency is 88.5%.  The fan motor input power is calculated to be:

1 Motor x 10 HP x 746 Watts x 100% assumed loading = 8,135 Watts
               Motor             HP        91.7% efficiency

The pump motor input power is calculated to be:

1 Motor x 2 HP x 746 Watts x 100% assumed loading = 1,686 Watts
               Motor             HP        88.5% efficiency

The combined input power is therefore:

8,135 Watts + 1,686 Watts = 9,821 Watts

Note:  Actual motor power should be used when available (see note in text).

Finally, the efficiency of the condenser is:

(2,105 MBH x 1,000 Btuh) / 9,821 Watts = 214 Btuh/Watt
                        MBH

214 Btuh per Watt is higher than the 160 Btuh per Watt requirement; this condenser meets the minimum efficiency requirements.

Air-cooled condensers shall have a fin density no greater than 10 fins per inch.  Condensers with higher fin densities have a higher risk of fouling with airborne debris.  This requirement does not apply for air-cooled condensers that utilize a micro-channel heat exchange surface, since this type of surface is not as susceptible to permanent fouling in the same manner as traditional tube-and-fin condensers with tight fin spacing.

The fin spacing requirement does not apply to condensers that are reused for an addition or alteration.

10.5.3  Compressor System Mandatory Requirements

This section addresses mandatory requirements for remote compressor systems and condensing units used for refrigeration.  'In addition to the requirements described below, all the compressors and all associated components must be designed to operate at a minimum condensing temperature of 70°F (21°C) or less.

A.   Floating Suction Pressure Controls

Compressors and multiple-compressor suction groups must have floating suction pressure control to reset the saturated suction pressure control setpoint based on the temperature requirements of the attached refrigeration display cases or walk-ins.

Exceptions to the floating suction pressure requirements are:

1.   Single compressor systems that do not have continuously variable capacity capability

2.   Suction groups that have a design saturated suction temperature of 30°F or higher

3.   Suction groups that comprise the high side of a two-stage or cascade system

4.   Suction groups that primarily serve chillers for secondary cooling fluids

5.   Existing compressor systems that are reused for an addition or alteration.

The examples of a two-stage system and a cascade system are shown in Figure 10-7  and Figure 10-8, respectively.  Figure 10-9 shows a secondary fluid system.

Figure 10-7 –Two-stage System using a Two-Stage Compressor

Figure 10-8 – Cascade System

Figure 10-9 – Secondary Fluid System

 

Example 10-15

Question

A retail food store has four suction groups, A, B1, B2 and C, with design saturated suction temperatures (SST) of   -22°F, -13°F, 28°F and 35°F, respectively.  System A is a condensing unit.   The compressor in the condensing unit is equipped with two unloaders.  Suction group B1 consists of a single compressor with no variable capacity capability.  Suction group B2 has four compressors with no variable capacity capability and suction group C has three compressors with no variable capacity capability.  Which of these suction groups are required to have floating suction pressure control?

Answer

Suction Group B1 is the only suction group that is not required to have a floating suction pressure control.  The rationale is explained below.

Suction group A: Although the suction group has only one compressor, the compressor has variable capacity capability in the form of unloaders.  Therefore, the suction group is required to have floating suction pressure control.

Suction group B1: The suction group has only one compressor with no variable capacity capability.  Therefore, the suction group is not required to have floating suction pressure control.

Suction group B2: Although the suction group has compressors with no variable capacity capability, the suction group has multiple compressors which can be sequenced to provide variable capacity capability.  Therefore, the suction group is required to have floating suction pressure control.

Suction group C: The design SST of the suction group is higher than 30°F.  Therefore, the suction group is not required to have floating suction pressure control.

 

Example 10-16

Question

A retail food store has two suction groups, a low temperature suction group A (-22°F design SST) and medium temperature suction group B (18°F design SST).  Suction group A consists of three compressors. Suction group B has four compressors that serve a glycol chiller working at 23°F.  Which of these suction groups are required to have floating suction pressure control?

Answer

Suction group A: The suction group has multiple compressors.  Therefore, the suction group is required to have floating suction pressure control.

Suction group B: Although the suction group has multiple compressors, it serves a chiller for secondary cooling fluid (glycol).  Therefore, the suction group is not required to have floating suction pressure control.

 

Example 10-17

Question

A retail food store is undergoing an expansion and has two refrigeration systems: an existing system and a new CO2 cascade system.  The existing system consists of four compressors and a design SST of 18°F.  The cascade refrigeration system consists of four low temperature compressors operating at -20°F SST and three medium temperature compressors operating at 26°F SST.  Which of these systems are required to have floating suction pressure control?

 

 

 

Answer

Existing system: Although the system has multiple compressors, the compressor system is being reused, and the existing rack controller and sensors may not support floating suction pressure control.  Therefore, the system is not required to have floating suction pressure control.

Cascade system: Only low temperature suction group of the system is required to have floating suction pressure control.

Evaporator coils are sized to maintain a design fixture temperature under design load conditions.  Design loads are high enough to cover the highest expected load throughout the year, and inherently include safety factors.  The actual load on evaporator coils varies throughout the day, month and year, and an evaporator coil operating at the design saturated evaporating temperature (SET) has excess capacity at most times.  The SET can be safely raised during these times, reducing evaporator capacity and reducing the required “lift” of the suction group, saving energy at the compressor while maintaining proper fixture (and product) temperature.

In a floating suction pressure control strategy, the suction group target saturated suction pressure (SST) setpoint is allowed to vary depending on the actual requirements of the attached loads, rather than fixing the SST setpoint low enough to satisfy the highest expected yearly load.  The target setpoint is adjusted so that it is just low enough to satisfy lowest current SET requirement of any attached refrigeration load while still maintaining target fixture temperatures, but not any higher.  The controls are typically bound by low and high setpoints limits.  The maximum float value should be established by the system designer, but a minimum value equal to the design SST (that is no negative float) and a positive float range of 4-6°F of saturation pressure equivalent have been used successfully.

Figure 10-10 shows hourly values for floating suction pressure control over a one week period, expressed in equivalent saturation temperature.  The suction pressure control setpoint is adjusted to meet the temperature setpoint at the most demanding fixture or walk-in.  The difference in SST between the floating suction pressure control and fixed suction pressure control translates into reduced compressor work and thus energy savings for the floating suction control.

Figure 10-10 – Example of Floating Suction Pressure Control

 

Floating Suction Pressure Control with Mechanical Evaporator Pressure Regulators

Mechanical evaporator pressure regulators (EPR valves) are often used on multiplex systems to maintain temperature by regulating the SET at each multiple evaporator connected to the common suction group, and often to also function as a suction-stop valve during defrost.  EPR valves throttle to maintain the pressure at the valve inlet and thus indirectly control the temperature at the case or walk-in.  The valves are manually adjusted to the pressure necessary to provide the desired fixture or walk-in air temperature.  The load (circuit) with the lowest EPR pressure governs the required compressor suction pressure setpoint.

Floating suction pressure on a system with EPR valves requires special attention to valve settings on the circuit(s) used for floating suction pressure control.  EPR valves on these circuit(s) must be adjusted “out of range”, meaning the EPR pressure must be set lower than what would otherwise be used to maintain temperature.  This keeps the EPR valve from interfering with the floating suction control logic.  In some control systems, two circuits are used to govern floating suction control; commonly designated as primary and secondary float circuits.  EPR valves may also be equipped with electrically controlled wide-open solenoid pilots for more fully automatic control if desired.

Similar logic is applied on systems using on/off liquid line solenoid valves (LLSV) for temperature control, with the control of the solenoid adjusted slightly out of range to avoid interference with floating suction pressure.

These procedures have been employed to float suction on supermarket control systems since the mid-80’s, however careful attention is still required during design, start-up and commissioning to insure control is effectively coordinated.

Figure 10-11 – Evaporators with Evaporative Pressure Regulator Valves

 

Floating Suction Pressure Control with Electronic Suction Regulators

An electronic suction regulator (ESR) valve is an electronically controlled valve used in the place of a mechanical evaporator pressure regulator valve.  ESRs are known in industry as electronic suction regulator (ESR) or electronic evaporator pressure regulator (EEPR).  It is important to note that ESR valves are not pressure regulators; instead they control the flow through the evaporator based on a setpoint air temperature at the case or walk-in.  ESR valves are modulated to maintain precise temperature.  This provides more accurate temperature compared to an EPR which controls temperature indirectly through pressure and is subject to pressure drop in piping and heat load (and thus TD) on the evaporator coil.

Floating suction pressure strategies with ESR valves vary depending on the controls manufacturer, but will generally allow for more flexibility than systems with EPR valves.  In general, the control system monitors how much each ESR valve is opened.  If an ESR is fully open, indicating that the evaporator connected to the ESR requires more capacity, the control system will respond by decrementing the SST setpoint.  If all ESR valves are less than fully open, the control system increments the suction pressure up until an ESR valve fully opens.  At this point, the control system starts floating down the suction pressure again.  This allows suction pressure to be no lower than necessary for the most demanding fixture.

Figure 10-12 shows multiple evaporators controlled by ESR valves connected to a common suction group.

Figure 10-12 – DX Evaporators with ESRs on a Multiplex System

 

B.   Liquid Subcooling

Liquid subcooling must be provided for all low temperature compressor systems with a design cooling capacity of 100,000 Btuh or greater and with a design saturated suction temperature of -10°F or lower.  The subcooled liquid temperature of 50°F or less must be maintained continuously at the exit of the subcooler.  Subcooling load may be handled by compressor economizer ports, or by using a suction group operating at a saturated suction temperature of 18°F or higher.    Figure 10-13 and Figure 10-14 show example subcooling configurations.

Figure 10-13 – Liquid Subcooling Provided by Scroll Compressor Economizer Ports

Figure 10-14 – Liquid Subcooling Provided By a Separate Medium-Temperature System

 

Exceptions to the liquid subcooling requirements are:

1.   Low temperature cascade systems that condense into another refrigeration system rather than condensing to ambient temperature

2.   Existing compressor systems that are reused for an addition or alteration

 

10.5.4  Refrigerated Display Case Lighting Control Requirements

All lighting in refrigerated display cases, and lights installed on glass doors of walk-in coolers and freezers shall be controlled by either automatic time switch controls and/or motion sensor control.  The requirements in this section apply to stores that are open for business for less than 140 hours per week.

Example 10-18

Question

A new store is open for business 24 hours a day but is closed on Sunday.  Do the display case lights at this store need to comply with the requirements of the Standards?

Answer

No.  This store is open for business 144 hours per week, and is therefore exempt.

 

Automatic Time Switch Control

Automatic time switch controls shall turn off the lights during non-business hours.

Timed overrides for a display case line-up or walk-in case may be used to turn on the lights for stocking or non-standard business hours.  The override must time-out and automatically turn the lights off again in one hour or less.  The override control may be enabled manually (e.g. a push button input to the control system) or may be scheduled by the lighting control or energy management system.

Motion Sensor

Motion sensor control can be used to meet this requirement by either dimming or turning off the display case lights when space near the case is vacated.  The lighting must dim so that the lighting power reduces to 50% or less.  The maximum time delay for the motion sensor must be 30 minutes or less.

10.5.5  Refrigeration Heat Recovery

This section addresses mandatory requirements for the use of heat recovery from refrigeration system(s) to HVAC system(s) for space heating and the charge limitations when implementing heat recovery, including an overview of configurations and design considerations for heat recovery systems.  Heat rejected from a refrigeration system is the total of the cooling load taken from display cases and walk-ins in the store plus the electric energy used by the refrigeration compressors.  Consequently, there is a natural relationship between the heat available and the heating needed; a store with greater refrigeration loads needs more heat to make up for the cases and walk-ins and also has more heat available.

The heat recovery requirements apply only to space heating.

There are many possible heat recovery design configurations due to the variety of refrigeration systems, HVAC systems and potential arrangement and locations of these systems.  A number of examples are presented here but the Standards do not require these configurations to be used.  The heat recovery design must be consistent with the other requirements in the Standards such as condenser floating head pressure.

At least 25 percent of the sum of the design Total Heat of Rejection (THR) of all refrigeration systems with individual design Total Heat of Rejection of 150,000 Btu/h or greater must be utilized for space heat recovery.

Exceptions to the above requirements for heat recovery are:

1.   Stores located in Climate Zone 15, which is the area around Palm Springs, California.  Weather and climate data are available in Joint Appendix JA2 – Reference Weather/Climate Data

2.   The above requirements for heat recovery do not apply to the HVAC and refrigeration systems that are reused for an addition or alteration

The Standards also limit the increase in hydrofluorocarbon (HFC) refrigerant charge associated with refrigeration heat recovery.  The increase in HFC refrigerant charge associated with refrigeration heat recovery equipment and piping must not be greater than 0.35 lbs. per 1,000 Btuh of heat recovery heating capacity.

Example 10-19

Question

A store has three new distributed refrigeration systems, A, B and C, with design Total Heat of Rejection (THR) of 140,000 Btuh, 230,000 Btu/h and 410,000 Btuh, respectively.  What is the minimum required amount of refrigeration heat recovery?

Answer

Refrigeration systems B and C have individual design THR of greater than 150,000 Btu/h, whereas refrigeration system A has design THR of less than 150,000 Btuh.  Therefore, the store must have the minimum refrigeration heat recovery equal to 25% of the sum of THR of refrigeration systems B and C only.  The minimum required heat recovery is therefore:

25% x (230,000 Btuh + 410,000 Btuh) = 160,000 Btuh

Example 10-20

Question

How should the Total Heat of Rejection be calculated for the purpose of this Section?

Answer

The THR value is equal to the total compressor capacity plus the compressor heat of compression. 

 

Example 10-21

Question

A 35,000 ft2 food store is undergoing an expansion to add 20,000 square feet area.  The store refrigeration designer plans to use two existing refrigeration systems with 600,000 Btu/h of design total heat rejection capacity and add a new refrigeration system with a design total heat rejection capacity of 320,000 Btu/h.  The store mechanical engineer plans on replacing all the existing HVAC units.  Is the store required to have refrigeration heat recovery for space heating?  

Answer

Yes.  The store must have the minimum required refrigeration heat recovery from the new refrigeration system.  The new refrigeration system has a design THR of greater than 150,000 Btu/h threshold.  The minimum amount of the refrigeration heat recovery is 25% of the new system THR.  The existing refrigeration systems are not required to have the refrigeration heat recovery.

A.   Refrigeration Heat Recovery Design Configurations

The designer of heat recovery systems must consider the arrangement of piping, valves, coils, and heat exchangers as applicable to meet the Standards of the code.  Numerous refrigeration heat recovery systems configurations are possible depending upon the refrigeration system type, HVAC system type and the store size.  Some possible configurations are:

1.   Direct heat recovery

2.   Indirect heat recovery

3.   Water loop heat pump system

These configurations are described in more detail with the following sections.

Direct Heat Recovery

Figure 10-15 shows a series-connected direct condensing heat recovery configuration.  In this configuration, the heat recovery coil is placed directly within the HVAC unit airstream (generally the unit serving the main sales area), and the discharge refrigerant vapor from the compressors is routed through the recovery coil and then to the outdoor refrigerant condenser when in heating mode.  If two or more refrigeration systems are used for heat recovery, a multi-circuit heat recovery coil could be used.

This configuration is very suitable when the compressor racks are close to the air handling unit that are to be used for heat recovery.  If the distance is too far, an alternative design should be considered; the long piping runs may result in a refrigerant charge increase that exceeds the maximum defined in the Standards, or there may be excessive pressure losses in the piping that could negatively affect compressor energy.

Figure 10-15 – Series Direct Heat Recovery Configuration

 

Figure 10-16 shows a parallel-connected direct-condensing configuration.  In this configuration, the heat recovery coil handles the entire condensing load for the connected refrigeration system(s) when the air handling unit is in heating mode.  Reduced refrigerant charge is the primary advantage of this configuration.  Since the unused condenser (either the heat recovery condenser or the outdoor condenser) can be pumped out, there is no increase in refrigerant charge.  A high degree of design expertise is required with this configuration in that the heat recovery condenser and associated HVAC system must take the entire heating load while operating at reasonable condensing temperatures—in any event, no higher than the system design SCT and in most instances with reasonable design no higher than 95°F-100°F condensing temperature in the heat recovery condenser.   Ducting with under case or low return air design is essential in this type of system, in order to obtain cooler entering air and maintain reasonable condensing temperatures.  Provision is required for practical factors such as dirty air filters.

Since the main condenser is not in use during heat recovery, the condenser floating head pressure requirements do not apply.

Figure 10-16 – Parallel Direct Condensing Heat Recovery Configuration

Indirect Heat Recovery

Figure 10-17shows an indirect heat recovery configuration with a fluid loop.  In this configuration, the recovered heat is transferred from the refrigerant to an intermediate fluid, normally water or water-glycol, which is circulated through a fluid-to-air heat exchanger located in the air handling unit airstream.  Like the direct condensing configuration, discharge refrigerant gas from the compressors is routed through the refrigerant-to-fluid heat exchanger and then to the outdoor refrigerant condenser when in heating mode.

The refrigerant-to-fluid heat exchanger can be located close to the refrigeration system compressors, maximizing the available heat for recover while keeping the overall refrigerant charge increase low.  This configuration is also suitable when multiple HVAC units are employed for the refrigeration heat recovery.  Indirect systems must utilize a circulation pump to circulate the fluid between the HVAC unit and the recovery heat exchanger.

Figure 10-17 – Indirect Heat Recovery with an Indirect Loop

     

Multiple refrigeration systems can also be connected in parallel or in series, using a common indirect fluid loop.  Figure 10-18 shows three refrigeration systems connected in series by a common fluid loop.  The temperatures shown are only examples.

 

Figure 10-18 – Series-Piped Indirect Water Recovery

 

This configuration allows the refrigerant-to-water condenser temperature difference (TD) to be kept low at each refrigeration system (e.g. 8°-10°F is possible) while maintaining a sufficiently high water-side TD at the air handling unit (e.g. 20°-25°F depending on specifics) to allow an effective selection of the water-to-air heating coil vs. the available airflow.  This method also minimizes both the required fluid flow and pump power.

B.   Control Considerations

Holdback Considerations

For direct and indirect systems, a holdback valve is required to control the refrigerant condensing temperature in the heat recovery coil (for direct systems) or the refrigerant-to-water condenser (for indirect systems) during heat recovery operation.  Regulating the refrigerant pressure to achieve condensing recovers the latent heat from the refrigerant.  Without condensing, only the sensible heat (i.e. superheat) is obtained, which is only a small fraction of the available heat. Figure 10-19   is a pressure-enthalpy diagram showing the difference in available recovery heat from a refrigeration system with and without a holdback valve.

Figure 10-19 – Pressure-Enthalpy Diagram with and without a Holdback Valve

 

The holdback valve regulates pressure at its inlet, and is located at the exit of the recovery heat exchanger.   Figure 10-20 shows a direct-condensing configuration with the proper location of the holdback valve.

Figure 10-20 – Direct-condensing configuration showing location of holdback valve

A more advanced design uses an electronic holdback valve controlled based on the temperature of the air entering the heat recovery coil.  The electronic heat recovery holdback valve controls the valve inlet pressure and thus the heat recovery coil condensing temperature to maintain only the pressure necessary to achieve the required condensing TD (heat recovery SCT less entering air temperature) thereby minimizing compressor efficiency penalty.  This is particularly useful when the volume outside air can significantly change the mixed air temperature entering the heat recovery coil.  In colder climates, reducing the heat recovery holdback pressure can be important as a means to avoid over-condensing (i.e. subcooling).  As shown in the pressure-enthalpy diagram above, there is additional flash gas handled by the condenser (even if the refrigerant fully condenses in the heat recovery coil) which is necessary to maintain piping and condenser velocity and thus minimize the charge in the outdoor condenser.

Other designs can replace the three-way valve with a differential pressure regulator and solenoid valve.  Figure 10-21 shows a direct-condensing configuration with an electronic heat recovery holdback valve, solenoid valve, and differential pressure regulator.

Figure 10-21 – Direct-condensing configuration showing differential regulator, solenoid valve, electronic holdback valve

 

Heat recovery and Floating Head Pressure

There is typically a tradeoff between heat recovery and refrigeration system efficiency, in that compressor discharge pressure must be increased to provide condensing for heat recovery.  If implemented properly, the electric penalty at the refrigeration system compressors is small compared to the heating energy savings.

The Standards require that the minimum condensing temperature at the refrigeration condenser shall be 70°F or less.  That means that (in the typical case of series-connected heat recovery) the refrigeration “cycle” still benefits from lower refrigerant liquid temperature, even if the compressor power is somewhat increased during heat recovery.  The pressure-enthalpy diagram shown in Figure 10-22 shows the incremental energy penalty at the refrigeration compressors due to the higher discharge pressure required for heat recovery, as well as the lower liquid temperature (and thus improved refrigerant cooling capacity) by floating head pressure at the outdoor condenser.

 

Figure 10-22 – Pressure-enthalpy diagram for heat recovery

 

C.   Recovery Coil Design Considerations

Recovery Coil Sizing Example

Selecting an appropriately-sized heat recovery coil is essential to proper heat recovery system operation.  The following example details the process of selecting a right-sized heat recovery coil.

Example 10-22

Question

A supermarket is being constructed that will utilize heat recovery.  The refrigeration system selected for recovery has the following parameters:

Design Refrigeration Load: 455.8 MBH

System design SST: 24°F

Representative Compressor Capacity at Design Conditions: 54.2 MBH

Representative Compressor Power at Design Conditions: 5.59 kW

The HVAC system serving the supermarket sales area is a central air handling unit.  Heat recovery will be accomplished with a direct-condensing recovery coil inside the air handling unit, downstream of both the return air duct and the outside air damper.  The air handling unit has the following design parameters:

Design Air Volume: 25,000 CFM

Design Coil Face Area: 41.7 SQ. FT.

To avoid excessive pressure drop across the recovery coil, the designer will select a coil with a fin density of 10 fins per inch.  The heat recovery circuit will use a holdback valve set at 95°F SCT.

What is the procedure for selecting a heat recovery coil?

Answer

To size a heat recovery system, the designer should first establish a design recovery coil capacity by analyzing the refrigeration system from which heat will be recovered.  Best practice dictates that the recovery system should be sized to recovery most of the available system total heat of rejection at typical operating conditions, not peak conditions.  Since we are designing for average operating conditions, the designer assumes the average refrigeration load is 70% of the design load.  Therefore, the average system THR for heating design is:

Average System THR = 70% x Design Refrigeration Load x THR Adjustment Factor

 

where:

THR Adjustments Factor = Representative Compressor THR
                                        Representative Compressor Capacity

and:

Rep. Compressor THR = Rep. Compressor Capacity + Rep. Compressor Heat of Compression

Using values from the example:
Representative Compressor THR = 54.2MBH + (5.50 kW x 3.415 MBH)
                                                                                                   kW
Representative Compressor THR = 73.3 MBH

Therefore,
THR Adjustment Factor = 73.3 MBH
                                       54.2 MBH
THR Adjustment Factor = 1.35

Using the values in this example and the calculated THR Adjustment Factor, the average system THR is:

Average system THR = 70% x 455.8 MBH x1.35


Average system THR = 430.1 MBH

It is important to note that the recovery system will not be capable of extracting 100% of the total heat of rejection since the condenser operates at a lower pressure and will reject additional heat, even if the heat recovery coil achieves full condensing.  'In addition, the heat recovery coil performance may often be limited by the available airflow across the coil and the consequent temperature rise vs. the heat being transferred.  This performance is determined through evaluation of coil performance, considering entering air temperature, and condensing temperature, as well as the coil design (e.g. rows, fins, air velocity and other factors).  Airside pressure drop can be minimized by using a larger face area, requiring lower face velocity and fewer rows.

For in this example, it was assumed that after evaluating coil performance, 85% of the average THR could be recovered with a reasonable coil velocity and coil depth.

Available Heat for Reclaim = 85% x Average System THR

Available Heat for Reclaim = 85% x 430.1 MBH

Available heat for Reclaim = 365.6 MBH

The available heat for recovery is the design capacity of the recovery coil we will select for our air handling unit.

Next, the designer needs to know the face velocity of the airstream in the air handling unit.  The face velocity is:

F.V. = Design CFM
         AHU Face Area

F.V. = 25,000 CFM
            41.7 ft2

F.V. = 600 ft/min

Finally, the designer needs to know the temperature difference between the condensing temperature (inside the recovery coil) and the temperature of the air entering the recovery coil.  Since the coil will be installed in an air handling unit downstream of the outside air damper, the designer assumes that the air entering the coil is a mix of return air from the store and outside air.  The designer must determine an appropriate design temperature for the air entering the recovery coil (Entering Air Temperature or EAT) during average heating hours, which is this instance was determined to be 65°F.  From the example, the heat recovery system will have a holdback valve setting of 95°F SCT.  Therefore, the temperature difference is:

TD = SCT – EAT

TD = 95oF - 65 oF

TD = 30 oF

 

Using the face velocity, design coil capacity, and temperature difference between condensing temperature and entering air temperature, the designer then refers to the air handling unit catalog to select a recovery coil.  Then the designer uses the following two tables:

The designer enters the first table with the calculated TD of 30°F, finding a correction factor of 0.6.  We enter the second table with the value:

MBH per SQ FT = (Design Coil Capacity) / Correction Factor
                                 Coil Face Area

MBH per SQ FT = (4184 MBH) / 0.6
                                41.7 ft2

MBH per SQ FT = 16.72

Per design requirements, the designer will select a 10 fin-per-inch coil.  From the second table, the designer selects the 3-row, 10 fin-per-inch coil for this application.

More commonly, computerized selection tools are used to select heat recovery coils, allowing vendors to provide multiple selections for comparison.

Air-side Integration Considerations

Return Air Location

In supermarkets, ducting return air from behind display cases or near the floor is beneficial in improving comfort by removing the stagnant cool air that naturally occurs due to product refrigeration cases.  This approach also increases the effectiveness of refrigeration heat recovery by increasing the temperature difference between the return air temperature and the refrigerant condensing temperature in the heat recovery coil. Figure 10-23  shows the location of an HVAC return air duct positioned to scavenge cool air from the floor level near refrigerated display cases.

Figure 10-23 – Low Return Air Example

 

Return Air Duct Configuration

Heat recovery can be incorporated into rooftop HVAC units (RTU) by installing the heat recovery coil inside the RTU cabinet or by installing in the return air duct upstream of the RTU, as shown in Figure 10-24.  Location inside the RTU is preferable when outside air is a substantial part of the heating load, but location in the return air duct is reasonable and can provide greater flexibility in selecting the heat recovery coil (e.g. for low face velocity and pressure drop), particularly when coupled with low return air on units located in the refrigerated space, which predominantly provide heating.  The fan design must allow for the additional ductwork and coil pressure drop.

 

Figure 10-24 – Heat Recovery Coil in Return Air Duct

 

Transfer Fan Configuration

A ducted transfer system is sometimes employed to remove cold air from aisles with refrigerated display cases (rather than blowing warm air into the refrigerated areas) and can be an easy and appropriate way to utilize heat recovery, particularly from smaller distributed systems. Figure 10- 25 depicts a ducted transfer system.

Figure 10-25 – Ducted Transfer System

            Calculating Charge Increase

The Standards require that the increase in HFC refrigerant charge from all equipment related to heat recovery for space heating shall be less than 0.35 lbs. for every 1,000 Btuh of heat recovery capacity at design conditions.  Refrigerant charge may increase due to the addition of the recovery coil itself (either the refrigerant-to-air heat exchanger for direct configurations, or the refrigerant-to-water heat exchanger for indirect configurations), and the additional piping between the compressor group and the recovery coil.  'In addition, the refrigerant leaving the recovery coil and entering the refrigerant condenser will be mostly condensed, which increases the charge in the outdoor condenser compared with normal operation. Operating the outdoor condenser at lower pressure (i.e. the required floating heat pressure control) vs. the higher setting at the heat recovery coil holdback valve creates pressure drop, flashing of some liquid to vapor and an increase in velocity due to the much larger volume of a pound of vapor vs. a point of liquid refrigerant.  Split condenser control, which is very common in cooler climates, can also be used to close-off and pump out half of the outdoor condenser.

It is the responsibility of the system designer to fully understand how the heat recovery system affects overall refrigerant charge.

Example 10-23

Question

A heat recovery system is being designed for a new supermarket.  The refrigerant is R-404A.  The proposed design is shown below:

 

Which piping runs should be included in the calculation of refrigerant charge increase in the proposed design?

Answer

Only the additional piping required to route the refrigerant to the heat recovery coil needs to be considered in this calculation.  The piping runs shown in red in the following figure should be included in the calculation of refrigerant charge increase from heat recovery.

 

 

 

Example 10-24

Question

What is the refrigerant charge size increase in the example described above?

Answer

The system designer prepares the following analysis to calculate the charge size in the refrigerant piping

 

The outdoor condenser has a capacity of 350 MBH at a TD of 10°F.  Using manufacturers published data, the designer determines that the condenser normal operating charge (without heat recovery) is 26.9 lbs.  To calculate the charge increase in the condenser due to heat reclaim, the designer estimates the condenser could be as much as 75% full of liquid, resulting in a condenser charge of 68.8 lbs. with heat recovery.

The heat recovery coil has a capacity of 320 MBH at a design TD of 20°F.  The system designer uses manufacturer’s documentation to determine that the heat recovery coil refrigerant charge is 14.1 lbs.

The total refrigerant charge with heat recovery is:

32.2 lbs ) piping + 68.8 lbs (system condenser) + 14.1 lbs (recovery coil) = 115.1 lbs

Therefore, the refrigerant charge increase with heat recovery is:

115.1 lbs – 26.9 lbs = 88.2 lbs

 

 

Example 10-25

Question

In the example above, does the recovery design comply with the requirement in the Standards that the recovery design shall utilize at least 25% of the design Total Heat of Rejection (THR) of the refrigeration system?

Answer

The system designer determines that the total THR of all the refrigeration systems in the new supermarket is 800 MBH.  From the previous example, the heat recovery capacity is 320 MBH.


 100 % x 320 MBH = 40%
               800 MBH

Therefore, the design is in compliance with the Standards.

 

Example 10-26

Question

In the example above, does the recovery design comply with the requirement in the Standards that the recovery design shall not increase the refrigerant charge size by more than 0.35 lbs. of refrigerant per 1,000 Btuh of recovery capacity?

Answer

From the previous example, the recovery capacity is 320 MBH at design conditions, and the total refrigerant charge size increase is 88.2 lbs.

 88.2 lbs  = 0.28 lbs/Btuh
 320 MBH

Since the refrigerant charge increases by less than 0.35 lbs./MBH, this design is in compliance with the Standards.

 

D.   Water Loop Heat Pump Heat Recovery

Water-source heat pumps (WLHP) can be used for in conjunction with water cooled refrigeration systems, connected to a common water loop as shown in Figure 10-26.  Refrigeration systems heat pumps serving various zones of the store reject heat into a water loop, which in turn is rejected to ambient by an evaporative fluid cooler.  When the heat pumps are in heating mode, they extract the heat rejected by the refrigeration systems from the water loop.  Additional heat, if required, is provided by a boiler connected to the water loop.  A significant advantage of this design is low refrigerant charge, since the refrigeration systems use a compact water-cooled condenser, typically with less charge than an air-cooled condenser and no heat recovery condenser is required.  Compared with other methods, however, the electric penalty is somewhat higher to utilize the available heat.

The floating pressure requirements in the standard would apply to the fluid coolers, i.e. controls to allow refrigeration systems to float to 70°F SCT and use of wetbulb following control logic.

Figure 10-26 – Water Loop Heat Pump Example

10.5.6  Additions and Alterations

Requirements related to commercial refrigeration additions and alterations to existing buildings are covered by the Standards in Section §141.1(b).  The specific requirements for additions and alterations for Commercial Refrigeration are included in §120.6(b).

10.5.7  Compliance Documentation

Compliance documentation includes the forms, reports and other information that are submitted to the enforcement agency with an application for a building permit (Certificate of Compliance). Compliance documentation also includes documentation completed by the installing contractor, engineer/architect of record, or owner’s agent to verify that certain systems and equipment have been correctly installed and commissioned (Installation Certificate).

A.   Form NRCC-PRC-05-E for Commercial Refrigeration - Certificate of Compliance

NRCC-PRC-05-E is the primary form for commercial refrigeration in retail food stores, which provides compliance information for the use of the enforcement agency’s field inspectors.  This form must be included on the plans.  A copy of this form should also be submitted to the enforcement agency along with the rest of the compliance submittal at the time of building permit application.  With enforcement agency approval, the applicant may use alternative formats of these forms (rather than the Energy Commission’s forms), provided the information is the same and in similar format.

NRCC-PRC-05-E: Project Information

Project Description

Project Name is the title of the project, as shown on the plans and known to the enforcement agency.

Climate Zone is the California Climate Zone in which the project is located.  See Reference Joint Appendix JA2 for a listing of climate zones.

Conditioned Floor Area has a specific meaning under the Standards.  The number entered here should match the floor area entered on the other forms.

Project Address is the address of the project as shown on the plans and known to the enforcement agency.

Date is the last revision date of the plans.  If the plans are revised after this date, it may be necessary to re-submit the compliance documentation to reflect the altered design.  Note that it is the enforcement agency‘s discretion whether to require new compliance documentation or not.

Building Area, the checkboxes are used to determine if the retail food store conditioned area is greater than or equal to 8,000 square feet.  If the retail food store conditioned area is less than 8,000 square feet then the retail food store need not comply with the Commercial Refrigeration requirements.

PHASE OF CONSTRUCTION indicates the status of the building project described in the compliance documents.  Refer to Section 1.7 for detailed discussion of the various choices.

NEW CONSTRUCTION should be checked for all new buildings, newly conditioned space or for new construction in existing buildings (tenant improvements, see Section 1.7.11 and 1.7.12) that are submitted for envelope compliance.

ADDITION should be checked for an addition which is not treated as a stand-alone building, but which uses option 2 described in Section 1.7.14.  Tenant improvements that increase conditioned floor area and volume are additions.

ALTERATION should be checked for alterations to an existing building mechanical systems (see Section 1.7.13).  Tenant improvements are usually alterations.

Documentation Author’s Declaration Statement

The Certificate of Compliance is signed by both the Documentation Author and the Principal Retail Food Store Designer who is responsible for preparation of the plans of building.  This latter person is also responsible for the energy compliance documentation, even if the actual work is delegated to a different person acting as Documentation Author.  It is necessary that the compliance documentation be consistent with the plans.

DOCUMENTATION AUTHOR is the person who prepared the energy compliance documentation and who signs the Declaration Statement.  The person’s telephone number is given to facilitate response to any questions that arise.  A Documentation Author may have additional certifications such as an Energy Analyst or a Certified Energy Plans Examiner certification number.  Enter number in the EA# or CEPE# box.

Principle Retail Food Store Designer’s Declaration Statement

The Declaration Statement is signed by the person responsible for preparation of the plans for the building.  This principal designer is also responsible for the energy compliance documentation, even if the actual work is delegated to someone else (the Documentation Author as described above).  It is necessary that the compliance documentation be consistent with the plans.  The Business and Professions Code governs who is qualified to prepare plans and therefore to sign this statement.  See Section 2.2.2 Permit Application for applicable text from the Business and Professions Code.

Mandatory Commercial Refrigeration Measures Note Block

The person with overall responsibility must ensure that the Mandatory Measures that apply to the project are 'listed on the plans. The format of the list is left to the discretion of the Principal Retail Food Store Designer.  A sample note block is shown below.

Commercial Refrigeration Mandatory Measures

Condensers (§120.6(b)1)

□    All condenser fans for air-cooled condensers, evaporative-cooled condensers, air –or water—cooled fluid coolers or cooling towers shall be continuously variable speed, with the speed of all fans serving a common condenser high side controlled in unison.

□     The refrigeration system condenser controls shall use variable setpoint control logic to reset the condensing temperature setpoint in response to ambient drybulb temperature for systems with air-cooled condensers and ambient wetbulb temperature for systems with evaporative-cooled condensers.

□     The minimum condensing temperature setpoint shall be less than or equal to 70°F.

□     Condenser Specific Efficiency.  Air-cooled condensers shall have specific efficiency of at least 65 Btuh/W and evaporative-cooled condenser shall have a specific efficiency of at least 160 Btuh/W.

□     Air-cooled condensers shall have a fin density no greater than 10 fins per inch.

Compressor Systems (§120.6(b)2)

□     Multiple compressor suction groups shall include control systems that use floating suction pressure logic to reset the target saturated suction temperature based on the temperature requirements of the attached refrigeration display cases or walk-ins.

□     Liquid subcooling shall be provided for all low temperature compressor systems with a design cooling capacity equal or greater than 100,000 Btuh with a design saturated suction temperature of -10°F or lower, with the subcooled liquid temperature maintained continuously at 50°F or less at the exit of the subcooler, using compressor economizer port(s) or a separate medium or high temperature suction group operating at a saturated suction temperature of 18°F or higher.

Refrigerated Display Cases (§120.6(b)3)

□     Lighting in refrigerated display cases, and lights on glass doors installed on walk-in coolers and freezers shall be controlled by one of the following: automatic time switch to turn off lights during non-business hours or motion sensor controls that reduce case lighting power by at least 50% within 30 minutes after the area near the case is vacated.

Refrigeration Heat Recovery (§120.6(b)4)

□     HVAC systems shall utilize heat recovery from refrigeration system(s) for space heating, using no less than 25% percent of the sum of the design Total Heat of Rejection of all refrigeration systems that have individual Total Heat of Rejection values of 150,000 Btu/h or greater at design conditions.

□     The increase in hydrofluorocarbon (HFC) refrigerant charge associated with refrigeration heat recovery equipment and piping shall be no greater than 0.35 lbs. per 1,000 Btu/h of heat recovery heating capacity.

NRCC-PRC-05-E (Page 2 of 4 through Page 4 of 4): Mandatory Requirements

Pages 2 through 4 of the NRCC-PRC-05-E form include the mandatory requirements for Commercial Refrigeration – Condensers, Compressor Systems, Refrigerated Display Cases and Heat Recovery Systems.  As stated on these pages, the required information should be either 'listed on the form or the page from the plans or specifications section and the paragraph displaying the required information should be indicated on the form.

NRCC-PRC-05-E: Fan-Powered Condenser Specific Efficiency Worksheet                                                              

Form NRCC-PRC-05-E (Fan-Powered Condenser Specific Efficiency Worksheet) shall be completed and submitted for retail food stores greater than 8,000 square feet or more when a new condenser is being installed. This form is not required to be on the plans (they may be submitted separately in the energy compliance package), or they may be included on the plans.