10.6 Refrigerated Warehouses

10.6.1  Overview

This chapter of the nonresidential compliance manual addresses refrigerated warehouses.  The Standards described in this chapter of the manual address refrigerated space insulation levels, underslab heating requirements in freezers, infiltration barriers, evaporator fan controls, condenser sizing and efficiency requirements, condenser fan controls, and screw compressor variable speed requirements.

A.   Organization and Content

This section of the manual focuses on Standards provisions unique to refrigerated warehouses. All buildings regulated under Part 6 of Title 24 must also comply with the General Provisions of the Standards (§100.0 – §100.2, §110.0 – §110.10, §120.0 – §120.9, §130.0 – §130.5), and additions and alterations requirements (§141.1).  These topics are generally addressed in Chapter 3 of this manual.

This chapter is organized as follows:

•      Section 10.6.1 Overview

•      Section 10.6.2 Building Envelope Mandatory Requirements

•      Section 10.6.3 Mechanical Systems Mandatory Requirements

•      Section 10.6.4 Additions and Alterations

•      Section 10.6.5 Compliance Documentation

B.   Mandatory Measures and Compliance Approaches

The energy efficiency requirements for refrigerated warehouses are all mandatory. There are no prescriptive requirements or performance compliance paths for refrigerated warehouses. Since the provisions are all mandatory, there are no trade-offs allowed between the various requirements. The application must demonstrate compliance with each of the mandatory measures. Exceptions to each mandatory requirement where provided are described in each of the mandatory measure sections below.

C.   What’s New in the 2013 Standards

With the update to the Standards, there are several important changes to the Refrigerated Warehouses requirements.  First, refrigerated warehouses and associated refrigeration equipment are regarded as “covered processes” in Title 24, which are now covered in Section §120.6.  Other changes to the Refrigerated Warehouses requirements include:

•      Increased freezer roof R-value requirements

•      Reduced freezer floor R-value requirements, with a new exception for freezers with underslab slab heat that is provided from the refrigeration system in a manner that produces productive cooling

•      Requirements for infiltration barriers on passageways between spaces

•      Evaporator fan control requirements for suction groups consisting of a single compressor without variable capacity capability, which were previously exempted

•      Allow air-cooled refrigeration condensers on systems that utilize ammonia as the refrigerant

•      Minimum efficiency requirements for air-cooled and evaporative condensers

•      Application-specific variable-speed requirements for single-compressor suction groups utilizing a screw compressor instead of equipment part-load efficiency requirements

Refrigeration system acceptance requirements

D.   Scope and Application

§120.6(a) of the Standards addresses the energy efficiency of refrigerated spaces within buildings, including coolers and freezers, as well as the refrigeration equipment that serves those spaces.  Coolers are defined as refrigerated spaces designed to operate at or above 28°F (-2°C) and at or below 55°F (13°C).  Freezers are defined as refrigerated spaces designed to operate below 28°F (-2°C).  The subsections of §120.6(a) that cover refrigerated space requirements are 1, 2, 3, 6, and 7.  The Building Energy Efficiency Standards do not address walk-in coolers and freezers, as these are covered by the Appliance Efficiency Regulations (Title 20).  A walk-in is defined as a refrigerated space that is less than 3,000 ft² in floor area.  However, refrigeration systems (compressors and condensers that have a common refrigerant supply) that serve a sum total of 3,000 ft² or more are required to comply with the subsections of §120.6(a) that addresses those components specifically (subsections 4, 5, and 7).  Also note that refrigeration systems and refrigerated display fixtures in grocery stores are covered in Section 120.6(b) and are described in Section 10.5 of this manual.

Additionally, areas within refrigerated warehouses designed solely for the purpose of quick chilling or quick freezing of products are exempt from the Standards.  Quick chilling and freezing spaces are defined as spaces with a design refrigeration evaporator load of greater than 240 Btu/hr-ft² of floor space, which is equivalent to 2 tons per 100 ft² of floor space.  A space used for quick chilling or freezing and also used for refrigerated storage must still meet the requirements of §120.6(a).

The intent of the Standards is to regulate storage space, not quick chilling or freezing space, or process equipment.  Recognizing that there is often a variety of space types and equipment connected to a particular suction group in a refrigerated warehouse, it is not always possible to identify compressor plant equipment that serves the storage space only.  It would be outside the intent of the Standards to apply the compressor plant requirements to an industrial process that is not covered by the Standards simply because a small storage space is also attached to the suction group.  Similarly, it would be outside of the intent of the Standards to exclude a compressor plant connected to a suction group serving a large storage space covered by the Standards on the basis of a small process cooler or quick chill space also connected to the same suction group.  For the purposes of compliance with the Standards, the compressor plant requirements apply when 80 percent or more of the design refrigeration capacity connected to the suction group is from refrigerated storage space(s).  A suction group refers to one or more compressors that are connected to one or more refrigeration loads, whose suction inlets share a common suction header or manifold.

A variety of space types and processes may be served by a compressor plant at different suction pressures.  When all of these compressors share a common condensing loop, it is impossible to address only the equipment serving refrigerated storage spaces.  For the purposes of compliance with the Standards, the provisions addressing condensers, subsection 4, apply only to new condensers that are part of new refrigeration systems when the total design capacity of all refrigerated storage spaces served by compressors using a common condensing loop is greater than or equal to 80 percent of the total design capacity.

'In 'addition to an all-new refrigerated facility, the Standards cover expansions and modifications to an existing facility and an existing refrigeration plant.  The Standards do not require that all existing equipment must all comply when a refrigerated warehouse is expanded or modified using existing refrigeration equipment.  Exceptions are stated in the individual equipment requirements and an explanation of applicability to Additions and Alterations is included in Section 10.4.

E.   Ventilation

Section §120.1(a)1 of the Standards concerning ventilation requirements includes an exception for “Refrigerated warehouses and other spaces or buildings that are not normally used for human occupancy and work”.  The definition of refrigerated warehouses covers all refrigerated spaces at or below 55°F (13°C) which will in some instances include spaces with occupancy levels or durations, effect of stored product on space conditions, or other factors which may require ventilation for one or more reasons.  Accordingly, while the Standards do not require ventilation for refrigerated warehouses, it is acknowledged that ventilation may be needed in some instances and is left to the determination of the owner and project engineer.

Example 10-27

Question

A space that is part of a refrigerated facility is used solely to freeze meat products and not for storage.  The design evaporator load is 310 Btu/hr-ft² at the applied conditions.  Does the space have to comply with the space requirements (subsections 1, 2, 3, 6, and 7) of the Standards?

Answer

No.  The design evaporator capacity is more than 240 Btu/hr-ft² and the space is not used for long-term storage.  This space meets the definition of a quick chilling space.  Therefore, the space does not have to comply with the space requirements (subsections 1, 2, 3, 6, and 7) of the Standards.

Example 10-28

Question

A refrigerated warehouse space is used to cool and store melons received from the field.  After the product temperature is pulled down, the product is stored in the same space for a few days until being shipped or sent to packaging.  The design evaporator capacity is 300 Btu/hr-ft2 at the applied conditions.  Does the space have to comply with the space requirements (subsections 1, 2, 3, 6, and 7) of the Standards?

Answer

Yes.  While the design evaporator capacity is greater than 240 Btu/hr-ft² and the space is used for product pull down for part of the time, the space is also used for holding product after it has been cooled.  Accordingly, the space has to comply with the space requirements (subsections 1, 2, 3, 6, and 7) of the Standards.

Comment:  The Standard does not define a specific time limit that a quick chill (which for clarity includes quick “freeze”) space could operate as a holding space (i.e. at full speed and thus full fan power).  The typical high fan power density in a quick chill space, particularly at full speed after the high cooling load has been removed, is very inefficient.  Thus a reasonable expectation for a dedicated quick chill space is to allow no more time (at full speed) than is appropriate to remove the product in a normal business cycle of loading, cooling/freezing, and removing product once it has been reduced to temperature. If product is to be held any longer, variable speed is required to reduce fan power. Variable speed requirements are discussed in under mechanical system requirements (sub-section 10.6.3B) of this Chapter 10.

Example 10-29

Question

A new refrigeration system serves both storage and quick chilling space.  The design refrigeration capacity of the storage space is 500 tons.  The design capacity of the quick chilling space is 50 tons.  Is the refrigeration system required to meet the requirements of the Standards?

Answer

Yes.  Since more than 80 percent of the design capacity of the system is serving storage space, the refrigeration system requirements apply.

Example 10-30

Question

A new refrigerated warehouse is being constructed, which will include a 1,500 ft² cooler space, and a 2,500 ft² freezer space.  Both the cooler and freezer are served by a common refrigeration system.  Is the refrigeration system required to comply with the Standard?

Answer

Since the cooler and freezer each have less than 3,000 ft² of floor area, they are not required to comply with the Standard.  However, they are considered walk-ins and must comply with the requirements of the Appliance Efficiency Regulations (Title 20).

Since the suction group serves a sum total 4,000 ft² of refrigerated floor area, the compressors and condenser are required to comply with subsections 4, 5, and 7 of Section §120.6(a), which specifically address refrigeration system requirements.

 

10.6.2  Building Envelope Mandatory Requirements

§120.6(a) subsections 1, 2, and 6 of the Standards address the mandatory requirements for refrigerated space insulation, underslab heating, and infiltration barriers.

A.   Envelope Insulation

Wall and Roof Insulation

Manufacturers must certify that insulating materials comply with California Quality Standards for Insulating Material (C.C.R., Title 24, Part 12, Chapters 12-13), which ensure that insulation sold or installed in the state performs according to stated R-values and meets minimum quality, health, and safety standards.  These Standards state that all thermal performance tests shall be conducted on materials which have been conditioned at 73.4° ± 3.6°F and a relative humidity of 50 ± 5 percent for 24 hours immediately preceding the tests. The average testing temperature shall be 75° ± 2°F with at least a 40°F temperature difference.  Builders may not install insulating materials unless the product has been certified by the Department of Consumer Affairs, Bureau of Home Furnishing and Thermal Insulation.  Builders and enforcement agencies shall use the Department of Consumer Affairs Directory of Certified Insulation Material to verify the certification of the insulating material. 

Refrigerated spaces with 3,000 ft² of floor area or more shall meet the minimum R-Value requirements shown in Table 10-3.

 

Table 10-3 – Refrigerated Warehouse Insulation

SPACE

SURFACE

MINIMUM R-VALUE (°F⋅hr⋅ft²/Btu)

Freezers

Roof/Ceiling

 

R-40

Wall

R-36

Floor

R-35

Floor with all heating from productive refrigeration capacity

R-20

Coolers

Roof/Ceiling

R-28

Wall

R-28

The R-values shown in Table 10-3 apply to all surfaces enclosing a refrigerated space, including refrigerated spaces adjoining conditioned spaces, other refrigerated spaces, unconditioned spaces and the outdoors.  If a partition is used between refrigerated spaces that are designed to always operate at the same temperature, the requirements do not apply.  The R-values are the nominal insulation R-values and do not include other building materials or internal or external “film” resistances.

 

Example 10-31

Question

A refrigerated warehouse designed to store produce at 45°F (7°C) is constructed from tilt-up concrete walls and concrete roof sections. What is the minimum R-value of the wall and roof insulation?

Answer

Since the storage temperature is greater than 28°F (-2°C), the space is defined as a cooler. The minimum R-value of the wall and roof insulation according to Table 10-3 is R-28.

 

Example 10-32

Question

A refrigerated warehouse is constructed of a wall section consisting of 4 inches of concrete, 6 inches of medium density (2 lb/ft³) foam insulation and another 4 inches of concrete. The nominal R-value of the foam insulation is R-5.8 per inch. What is the R-value of this wall section for code compliance purposes?

Answer

The insulating value of the concrete walls is ignored. The R-value of this wall section for code compliance purposes is based on the 6 inches of foam insulation at R-5.8 per inch, or R-34.8.

Example 10-33

Question

A 35°F cooler space is adjacent to a -10°F freezer space.  What is the minimum required insulation R-value of the shared wall between the cooler and freezer spaces?

Answer

The minimum insulation R-value requirements should be interpreted to apply to all surfaces enclosing the refrigerated space at the subject temperature.  Therefore, since the freezer space walls must be insulated to the minimum R-value requirements shown in Table 10-3, the R-value of the shared wall insulation must be at least R-36.  The minimum insulation R-value requirement of the other three cooler walls is R-28.  The figure below illustrates this example.

B.  Freezer Floor Insulation

Freezer spaces with 3,000 ft² of floor area or more shall meet the minimum floor insulation R-value requirements shown in Table 10-3.  The requirement is a minimum R-value of R-35, with an exception if the underslab heating system increases productive refrigeration capacity, in which case the minimum R-value is R-20.

The predominant insulating material used in freezer floors is extruded polystyrene, which is commonly available in 2”-thick increments, but can optionally be purchased in 1”-thick increments as well.  Extruded polystyrene has an R-value of R-5 per inch at standardized rating conditions, and extruded polystyrene panels can be stacked, so the freezer floor can be constructed with R-value multiples of 5 (R-30, R-35, R-40).

A lower floor insulation R-value of R-20 is allowed if all of the underslab heat is provided by an underslab heating system that increases productive refrigeration capacity.  An example of an underslab heating system utilizing heat from a refrigerant liquid subcooler is shown in Figure 10-27.

Figure 10-27– Underslab Heating System that Utilizes Refrigerant Subcooling

The lower R-value requirement when this type of underslab heating system is used is justified because the increased underslab heat gain to the space due to reduced insulation is offset by the heat extracted from the refrigerant liquid—which is a direct reduction in compressor load.  The minimum requirement of R-20 does not mean that R-20 is the optimum or appropriate insulation choice in all installations.  Rather, R-20 is a cost-effective trade-off when underfloor heating is obtained via productive refrigeration.  Higher insulation levels combined with heating from productive refrigeration would further improve efficiency.

B.   Underslab Heating Controls

Underslab heating systems should be used under freezer spaces to prevent soil freezing and expansion.  The underslab heating element might be electric resistance, forced air, or heated fluid; however, underslab heating systems utilizing electric resistance heating elements are not permitted unless they are thermostatically-controlled and disabled during the summer on-peak period.  The summer on-peak period is defined by the supplying electric utility, but generally occurs from approximately 12 PM to 6 PM weekdays during the months of May through October.  The control system used to control any electric resistance underslab heating elements must automatically turn the elements off during this on-peak period.  The control system used to control electric resistance underslab heating elements must be shown on the building drawings, and the control sequence demonstrating compliance with this requirement must be documented on the drawings and in the control system specifications.

 

C.   Infiltration Barriers

Passageways between freezers and higher-temperature spaces, and passageways between coolers and non-refrigerated spaces, shall have an infiltration barrier such as:

•      Strip curtains, or

•      An automatically closing door, or

•      Air curtain

Examples of each are shown below.

Figure 10-28 – Strip Curtains

 

Figure 10-29 – Bi-parting automatic door

Figure 10-30 – Hinged door with spring-action door closer and door “tight” closer

 

Figure 10-31 – Air Curtain

 

The passageways may be for, but are not limited to, people, forklifts, pallet lifts, hand-trucks, or conveyor belts.

Strip curtains are commercial flexible plastic strips made for refrigerated openings with material type, weight and overlap design, designed for the size of the passageway opening and the temperatures of the subject spaces.

An automatically closing door is a door that fully closes under its own power.  Examples include:

•      Single acting or double acting hinge-mounted doors with a spring assembly or cam-type gravity hinges.

•      Powered single-sliding, bi-parting or rollup doors which open based on a pull-cord, proximity or similar sensors, or by operator signal and close automatically through similar actions or after a period of time sufficient to allow passageway transit.

An air curtain is a commercial fan powered assembly intended to reduce air infiltration and designed by its manufacturer for use on refrigerated warehouse passageways, and for use on the opening size and the temperatures for which it is applied.

There are two exceptions to the requirements for infiltration barriers:

1.   Openings with less than 16 square feet of opening area, such as small passageways for conveyor belts

2.   Loading dock doorways for trailers

Example 10-34

Question

A refrigerated warehouse includes a freezer, cooler, a refrigerated dock, and a conditioned office, as shown in the following figure.  Where are infiltration barriers required?

 

 

Answer

Infiltration barrier are required between all spaces including the hinge-mounted doors between the dock and the office.  The dock doors do not require infiltration barriers.

 

Example 10-35

Question

A refrigerated warehouse is being constructed for a flower distribution company.  Strip curtains cannot be used on the doors because the strips will damage the flowers when the pallet jack passes through.  Is the warehouse still required to have infiltration barriers?

Answer

Yes, the warehouse is required to have infiltration barriers.  If strip curtains cannot be used, the designer may choose another method, such as double-acting hinged doors, sliding or rollup doors with automatic door closers.

 

D.   Acceptance Requirements

The Standards include acceptance test requirements for electric resistance underslab heating systems in accordance with NA7.10.1. The test requirements are described in Chapter 13 and the Reference Nonresidential Appendix NA7.10. The test requirements are described briefly in the following paragraph.

 

E.   Electric Resistance Underslab Heating System

The acceptance requirements include functional tests that are to be performed to verify that the electric resistance underslab heating system automatically turns off during a test on-peak period.

10.6.3  Mechanical Systems Mandatory Requirements

A.   Overview

This section addresses mandatory requirements for mechanical systems serving refrigerated spaces.  Mechanical system components addressed by the Standards include evaporators (air units), compressors, condensers, and refrigeration system controls.  The requirements for each of these components are described in the following sections.  The requirements apply to all system and component types with the exception of the specific exclusions noted in §120.6(a).  The following figures identify some of the common system and component configurations that fall under §120.6(a).

Figure 10-32 is a schematic of a single stage system with direct expansion (DX) evaporator coils. Figure 10-33 identifies a single stage system with flooded evaporator coils; while Figure 10-34 shows a single stage system with pump recirculated evaporators. Figure 10-35 is a schematic of a typical two-stage system with an intercooler between the compressor stages. Figure 10-36 is a single-stage system with a water-cooled condenser and fluid cooler.

 

Figure 10-32 – Single Stage System with DX Evaporator Coil

Figure 10-33– Single Stage System with Flooded Evaporator Coil

 

 

Figure 10-34 – Single Stage System with Pump Recirculated Evaporator Coils

 

 

Figure 10-35 – Two-Stage System with Flooded Evaporator Coil

 

Figure 10-36 – Single System with Water-Cooled Condenser Served by Fluid Cooler

 

B.   Evaporators

New fan-powered evaporators used in coolers and freezers must meet the fan motor type, efficiency, and fan control requirements outlined in the Standards.

a.   Allowed Fan Motor Types

Single phase fan motors less than 1 horsepower and less than 460 Volts must be either electronically-commutated (EC, also known as Brushless DC) or must have an efficiency of 70 percent or more when rated in accordance with NEMA Standard MG 1-2006 at full load rating conditions.  This requirement is designed to reduce fan power in small evaporator fans.

b.   Fan Motor Control

The speed of all evaporator fans served by either a suction group with multiple compressors or by a single compressor with variable capacity capability must be controlled in response to space temperature or humidity using a continuously variable speed control method.  Two-speed control of evaporator fans is not an acceptable control method.

The fan speed is controlled in response to space temperature or humidity.  Fan speed should increase proportionally when the space temperature is above setpoint and decrease when the space temperature is at or below setpoint, with refrigerant supply and pressure being maintained in the evaporator cooling coil.  Fan speed is equivalent to air volume being circulated, resulting in direct control of cooling capacity, analogous to “variable air volume” cooling in commercial buildings.  The control logic requires design and tuning to provide “variable” capacity operation.

The use of humidity as the control variable for speed control is very limited in practice but is included in the Standards to accommodate special strategies for humidity-sensitive perishable product.  Control logic is these applications often will employ humidity in conjunction with temperature.

The intent of this requirement is to take advantage of the “third-power” fan affinity law, which states that the percentage of required fan motor power is approximately equal to the cube of the percentage of fan speed, while the airflow is linearly proportional to the fan speed.  For example, a fan running at 80 percent speed requires approximately 51 percent (80%3 = 51%) power while providing approximately 80 percent airflow. (Figure 10-37) Actual power is somewhat higher due to inefficiencies and drive losses.  This shows the relationship between fan speed and both required fan power and approximate airflow.

There is no requirement in the Standards for the minimum speed setting (i.e. how low the fan speed must go at minimum load).  Variable speed controls of evaporator fans has commonly used minimum speeds of 80 percent or lower on direct expansion coils and 70 percent or lower on flooded or recirculated coils.  The allowable minimum fan speed setting is to be determined by the refrigeration system designer.  The fan speed may be adjusted or controlled to maintain adequate air circulation in order to ensure product integrity and quality.

Figure 10-37– Relationship between Fan Speed and Required Power



Correct fan speed control requires the associated system suction pressure to be controlled such that evaporator capacity is sufficient to meet space loads.  If the evaporator suction pressure is too high relative to the desired room temperature, the evaporator fans will run at excessively high speed and energy savings will not be realized.  If floating suction pressure automation is used to optimize the suction pressure setpoint, suction pressure should only be allowed to float up after fan speeds are at minimum and should be controlled to float back down prior to increasing fan speeds.

The Standards have three exceptions to the evaporator variable speed requirement:

1.         In case of a replacement, addition or alteration of existing evaporators with no variable speed control, the variable speed control of the evaporators is mandatory only if the replacement, addition or alteration is done for all the evaporators in an existing space. [Exception 1 to §120.6 (a) 3B]

2.         A Controlled Atmosphere (CA) storage where products that require 100 percent of the design airflow at all times are stored may be exempt from the variable speed control requirement.  A licensed engineer must certify that the products in the cooler require continuous airflow at 100 percent speed.  Variable speed control must be implemented if the space will also be used for non-CA product or operation. [Exception 2 to §120.6 (a) 3B]

3.         The variable speed control is not mandatory for spaces that are used solely for quick chilling or quick freezing of products.  Such spaces have design cooling capacities that are greater than 240 Btu/hr-ft² of floor area, which is equivalent to 2 tons per 100ft² of floor area.  However, variable speed control must be implemented if the spaces are used for storage for any length of time, regardless of how much refrigeration capacity is installed in the space. [Exception 3 to §120.6 (a) 3B].

Example 10-36

Question

A split system with a packaged air-cooled condensing unit with a single 30 HP compressor with unloaders serves two direct expansion evaporators in a 3,200 ft² cooler.  Are the evaporator fans required to have variable speed control?

Answer

Yes.  Since the compressor has a variable capacity capability in the form of unloaders, the evaporator fans are required to have variable speed control.

Example 10-37

Question

A refrigeration system utilizes two reciprocating compressors without variable capacity capability connected in parallel, and serves multiple evaporators in a 10,000 ft² cooler. Are the evaporator fans required to have variable speed control?

Answer

Yes.  Since the evaporators are served by more than one compressor, they must have variable speed control, even though the compressors are not equipped with capacity control devices (e.g. unloaders).

In practice, the designer should consider the steps of capacity necessary to allow stable control.  For small systems, the designer may consider use of control that proportionally controls both compressor capacity steps and speed steps in unison.  As long as this control scheme is in response to space temperature, it would be consistent with the Standards.

 

Example 10-38

Question

A -20°F (-29°C) freezer has a number of recirculated evaporator coils that were selected to meet the design load at a 10°F (5.5°C) temperature difference (TD). The evaporator fan motors utilize variable speed drives and the control system varies the fan speed in response to space temperature.  What should the freezer saturated suction temperature be in order to achieve proper control and savings – by allowing fan speed control to act as the primary means of temperature control.

Answer

Since the coils were designed at a 10°F (5.5°C) TD and the target freezer temperature is -20°F (-29°C), the saturated evaporating temperature should be -30°F (-34°C) (-20°F minus 10°F); with the compressor controlled at a lower temperature, based on the design piping pressure drop.  For example with 2°F (1°C) of piping losses, the compressor control setpoint would be -32°F (-36°C).

The purpose of this example is to show how evaporator temperature and coil capacity can be considered and maintained in order to achieve proper variable speed fan operation and savings.  Settings could be further fine-tuned through observation of the required suction pressure to meet cooling loads and achieve minimum fan speeds average load periods, yet with a suction pressure no lower than necessary.

Example 10-39

Question

An existing refrigerated warehouse space has eight existing evaporators that do not have variable speed control.  Six of the eight evaporators are being replaced with new evaporators.  Do the new evaporators require variable speed control?

Answer

No.  Since all the evaporators are not being replaced, the new evaporators do not require variable speed control.

The reason for this is that effective space temperature control would often require that the entire space utilize a consistent control scheme which could require a disproportional cost.  While not required by the Standards, in many instances it may still be very cost effective to add variable speed control to existing as well as new evaporators in this situation.

Continuously variable speed control is not mandatory for evaporators that are served by a single compressor that does not have variable capacity capability (i.e. the compressor cycles on and off in response to space temperature).  For these systems, evaporator airflow must be reduced by at least 40 percent when the compressor is off.  This can be accomplished in a number of ways, for example:

•      Two speed evaporator fan control, with speed reduced by at least 40% when cooling is satisfied and the compressor is off.

•      Turning off a portion of the fans in each evaporator to accomplish at least 40% reduction in fan power.  Typically baffles are required to prevent reverse flow through fans that are turned off.

•      Turning off all fans when the compressor is off.  With this strategy a duty cycle can be employed to provide period forced fan operation to maintain air circulation, if the “on” period is limited to 25% of the duty cycle while the compressor is off.

Example 10-40

Question

A split system with a packaged air-cooled condensing unit utilizing a single cycling compressor without unloaders serves two evaporators in a cooler.  Each evaporator has five fans.  What options does the system designer have to meet the requirements for evaporator coils served by a single cycling compressor?

 

 

Answer

Multiple methods can be used to reduce airflow by at least 40% when the compressor is off, or turn all fans off with a 25% duty cycle.

Example 1: The designer may specify two-speed fans, or utilize variable frequency drives or other speed-reduction devices to reduce the fan speed to 60% or less when the compressor is off.

Example 2: The designer may utilize controls that cycle at least four of the ten fans off when the compressor is cycled off.  This would most likely be accomplished by cycling two fans off on each evaporator.

 

C.   Condensers

New condensers on new refrigeration systems must follow the condenser sizing, fan control, and efficiency requirements as described in §120.6(a)4.

Condenser Sizing

Sections §120.6(a)4A and §120.6(a)4B describe minimum sizing requirements for new condensers serving new refrigeration systems.  Fan-powered evaporative condensers, as well as water-cooled condensers served by fluid coolers and cooling towers are covered in Section §120.6(a)4A.  Fan-powered air-cooled condensers are covered by Section §120.6(a)4B.

Condensers must be sized to provide sufficient heat rejection capacity under design conditions while maintaining a specified maximum temperature difference between the refrigeration system saturated condensing temperature (SCT) and ambient temperature.  The design condenser capacity shall be greater than the calculated combined Total Heat of Rejection (THR) of the dedicated compressors that are served by the condenser.  If multiple condensers are specified, then the combined capacity of the installed condensers shall be greater than the calculated heat of rejection.  When determining the design THR for the purpose of this requirement, reserve or backup compressors may be excluded from the calculations.

There is no limitation on the type of condenser that may be used.  The choice may be made by the system designer, considering the specific application, climate, water availability, etc.

The Standards include an exception to Sections §120.6(a)4A and 4B for condensers serving refrigeration systems for which more than 20% of the design cooling load comes from quick chilling or freezing space, or process (non-space) refrigeration cooling.  Title 24 defines quick chilling or freezing space as a space with a design refrigeration evaporator capacity greater than 240 Btu/hr-ft² of floor area, which is equivalent to 2 tons per 100ft² of floor area, at system design conditions.

The sizing requirements for air-cooled condensers (Sections §120.6(a)4B) do not apply to the condensers included in air-cooled condensing units.  Condensing units include compressor(s), condenser, liquid receiver, and control electronics are packaged in a single product.  However, this exception applies only if the compressor(s) in the condensing units have a nameplate size totaling less than 100HP.

Example 10-41

Question

A new food processing facility is being constructed that will include an 800ft² blast freezer, a holding freezer, and a loading dock.  The design evaporator capacity of the blast freezer is 40 TR (tons of refrigeration).  The combined evaporator capacity of the freezer and loading dock is 60 TR.  Does the condenser group have to comply with the sizing requirements in §120.6(a)4A?

Answer

The blast freezer evaporator capacity divided by the floor area is 100TR/800ft², which is equal to 12.5 TR/100ft².  That means this particular blast freezer is deemed quick freezing space by the Standards.  Therefore, the condenser group serving the refrigeration system does not have to comply with §120.6(a)4A, since 40% (i.e. greater than 20%) of the design refrigeration capacity is from quick freezing.

Example 10-42

Question

The refrigerated warehouse system shown below has a backup or “swing” compressor.  Does the heat rejection from this compressor need to be included in the condenser sizing calculations?

Answer

It depends.

A swing compressor may be designed solely for back-up of multiple suction groups or it may be included in one suction group and necessary to meet the design load of that suction group, but in an emergency is also capable of providing back-up for other compressors.  If the compressor is solely for use as back-up, it would be excluded from the heat rejection calculation for the purposes of the Standards. In this case, the calculations would include the heat of rejection from Compressors 2, 3, and 4 and would exclude Compressor 1.

 

Section 120.6(a)4A Sizing of Evaporative Condensers, Fluid Coolers, and Cooling Towers

Section §120.6(a)4A provides maximum design SCT values for evaporative condensers as well as systems consisting of a water-cooled condenser served by a cooling tower or fluid cooler.  For the purpose of this Section, designers should use the 0.5 percent design wet-bulb temperature (WBT) from Table 10-4 – Design Day Data for California Cities in the Reference Joint Appendices JA2 to demonstrate compliance with this requirement. The maximum design SCT requirements are 'listed in Table 10-4 below:Table 10-4 –Maximum Design SCT Requirements for Evaporative Condensers and Water-Cooled Condensers Served by Cooling Towers and Fluid Coolers

 

0.5% DESIGN WET-BULB TEMPERATURE

MAXIMUM DESIGN SCT

≤ 76°F (24°C)

Design WBT plus 20°F (11°C)

Between 76°F (24°C) and 78°F (26°C)

Design WBT plus 19°F (10.5°C)

≥ 78°F (26°C)

Design WBT plus 18°F (10°C)

 

Example 10-43

Question

A refrigerated warehouse is being constructed in Fresno, California.  The refrigeration system will be served by an evaporative condenser.  What is the sizing requirement for the condenser selected for this system?

Answer

The 0.5% design wetbulb temperature (WBT) from Joint Appendix JA-2 for Fresno, California, is 73°F.  Therefore, the maximum design SCT for the refrigerant condenser is 73°F + 20°F = 93°F.  The selected condenser for this system must be capable of rejecting the total system design THR at 93°F SCT, and 73°F WBT.

 

Example 10-44

Question

What is the minimum size for a condenser for a refrigeration system with the following parameters?

  Located in Fresno, California

  Design SST: 10°F

  Suction group: 3 equal-sized dedicated screw compressors (none are backup units)

  Evaporative condenser

  200 TR (tons refrigeration) cooling load

Answer

From the previous example, it was determined that the design wetbulb temperature (WBT) to demonstrate compliance for Fresno, California is 73°F and the maximum design SCT for the evaporative condenser is 93°F (73°F + 20°F).  We will assume the system designer determined a 2°F loss between the compressors and condenser.  The designer first calculates the total heat of rejection (THR) for the suction group at the design conditions of 10°F SST and 95°F SCT.  The selected compressors each have a rated capacity of 240 tons of refrigeration and will absorb 300 horsepower at the design conditions.  Therefore, the calculated THR for one compressor is:

240 TR /Compressor x 3 compressor x 12,000 Btuh/TR + 300HP x 2,545 Btuh/HP = 10,930,500 Btuh
                                         

To comply with the Standards, a condenser (or group of condensers) must be selected that is capable of rejecting at least 10,930,500 Btu/hr at 93°F SCT and 73°F WBT.

 

Section 120.6(a)4B Sizing of Air-Cooled Condensers

Section 120.6(a)4B provides maximum design SCT values for air-cooled condensers.  For the purpose of this Section, Designers should use the 0.5 percent design dry-bulb temperature (DBT) from Table 10-4– Design Day Data for California Cities in the Reference Joint Appendices JA2 to demonstrate compliance with this requirement. 

Standard practice is for published condenser ratings to assume the capacity of air-cooled condensers is proportional to the temperature difference (TD) between SCT and DBT, regardless of the actual ambient temperature entering the condenser.  For example, the capacity of an air-cooled condenser operating at an SCT of 80°F with a DBT of 70°F is assumed to be equal to the same unit operating at 110°F SCT and 100°F DBT, since the TD across the condenser is 10°F in both examples.  Thus, unlike evaporative condensers, the requirement for air-cooled condensers does not have varying sizing requirements for different design ambient temperatures.

However, the Standards have different requirements for air-cooled condensers depending on the space temperatures served by the refrigeration system.  The maximum design SCT requirements are 'listed in Table 10-5 below:.

Table 10-5 – Maximum Design SCT Requirements for Air-Cooled Condensers

 

REFRIGERATED SPACE TYPE

SPACE TEMPERATURE

MAXIMUM SCT

Cooler

 

≥ 28°F (-2°C)

Design DBT plus 15°F (8.3°C)

Freezer

 

< 28°F (-2°C)

Design DBT plus 10°F (5.6°C)

Often, a single refrigeration system and its associated condenser will serve a mix of cooler and freezer spaces.  In this instance, the maximum design SCT shall be a weighted average of the requirements for cooler and freezer spaces, based on the design evaporator capacity of the spaces served.

Example 10-45

Question

An air-cooled condenser is being sized for a system that has half of its installed capacity serving cooler space and the other half serving freezer space.  What is the design TD to be added to the design dry bulb temperature?

Answer

Using air-cooled condensers for coolers have a design approach of 15°F (8.3°C) and for freezers a design approach of 10°F (5.6°C).  When a system serves freezer and cooler spaces, a weighted average should be used based on the installed capacity.  To calculate the weighted average, multiply the percent of the total installed capacity dedicated to coolers by 15°F (8.3°C).  Next, multiply the percent of the total installed capacity dedicated to freezers by 10°F (5.6°C).  The sum of the two results is the design condensing temperature approach. In this example, the installed capacity is evenly split between freezer and cooler space.  As a result, the design approach for the air-cooled condenser is 12.5°F (6.9°C).

(50% x 15 oF) + (50% x 10oF) = 7.5 oF + 5 oF = 12.5 oF

Fan Control

Condenser fans for new air-cooled or evaporative condensers, or fans on cooling towers or fluid coolers used to reject heat on new refrigeration systems, must be continuously variable speed.  Variable frequency drives are commonly used to provide continuously variable speed control of condenser fans although controllers designed to vary the speed of electronically commutated motors may be used to control these types of motors.  All fans serving a common high side, or cooling water loop for cooling towers and fluid coolers, shall be controlled in unison.  Thus, in normal operation, the fan speed of all fans within a single condenser or set of condensers serving a common high-side should modulate together, rather than running fans at different speeds or staging fans off.  However, when fan speed is at the minimum practical level usually no higher than 10-20%, the fans may be staged off to further reduce condenser capacity.  As load increases, fans should be turned back on prior to significantly increasing fan speed, recognizing a control band is necessary to avoid excessive fan cycling.

To minimize overall system energy consumption, the condensing temperature setpoint must be continuously reset in response to ambient temperatures, rather than using a fixed setpoint value.  This strategy is also termed ambient-following control, ambient-reset, wetbulb following and drybulb following—all referring to control logic which changes the condensing temperature target in response to ambient conditions at the condenser.  The control system calculates a target saturated condensing temperature that is higher than the ambient temperature by a predetermined temperature difference (i.e. the condenser control TD).  Fan speed is then modulated according to the calculated target SCT.  The target SCT for evaporative condensers or water-cooled condensers (via cooling towers or fluid coolers) must be reset according to ambient wet bulb temperature, and the target SCT for air-cooled condensers must be reset according to ambient dry bulb temperature.

The condenser control TD is not specified in the Standards.  The nominal control value is often less than the condenser design TD; however the value for a particular system is left up to the system designer.  Since the intent is to utilize as much condenser capacity as possible without excessive fan power, common practice for refrigerated warehouse systems is to optimize the control TD over a period of time such that the fan speed is in a range of approximately 60-80% during normal operation (i.e. when not at minimum SCT).  While not required, evaporative condensers and systems utilizing fluid coolers and cooling towers may also vary the condenser control TD as a function of actual WBT, to account for the properties of moist air, which reduce the effective condenser capacity at lower wetbulb temperatures.

The minimum saturated condensing temperature setpoint must be 70°F (21°C) or less.  For systems utilizing halocarbon refrigerants with glide, the SCT setpoint shall correlate with a midpoint temperature (between the refrigerant bubble-point and dew point temperatures) of 70°F (21°C) or less.  As a practical matter, a maximum SCT setpoint is also commonly employed to set an upper bound on the control setpoint in the event of a sensor failure and to force full condenser operation during peak ambient conditions.  This value should be set high enough that it does not interfere with normal operation.

Split air-cooled condensers are sometimes used for separate refrigeration systems, with two circuits and two rows of condenser fans.  Each condenser half would be controlled as a separate condenser.  If a condenser has multiple circuits served by a common fan or set of fans, the control strategy may utilize the average condensing temperature or the highest condensing temperature of the individual circuits as the control variable for controlling fan speed.

Alternative control strategies are permitted to the condensing temperature reset control required in Section §120.6(a)4E.  The alternative control strategy must be demonstrated to provide equal or better performance, as approved by the Executive Director.

Example 10-46

Question

A refrigerated warehouse with evaporative condensers is being commissioned.  The control system designer has utilized a wet bulb-following control strategy to reset the system saturated condensing temperature (SCT) setpoint.  The refrigeration engineer has calculated that adding a TD of 15°F (8.3°C) above the ambient wet bulb temperature should provide a saturated condensing temperature setpoint that minimizes the combined compressor and condenser fan power usage throughout the year.  What might the system SCT and SCT setpoint trends look like over an example day?

Answer

The following figure illustrates what the actual saturated condensing temperature and SCT setpoints could be over an example day using the wet bulb-following control strategy with a 15°F (8.3°C) TD and also observing the 70°F (21°C) minimum condensing temperature requirement.  As the figure shows, the SCT setpoint is continuously reset to 15°F (8.3°C) above the ambient wet bulb temperature until the minimum SCT setpoint of 70°F is reached. The figure also shows a maximum SCT setpoint (in this example, 90°F (32.2°C) which may be utilized to limit the maximum control setpoint, regardless of the ambient temperature value or TD parameter.

Example 10-47

Question

A cold storage facility with an air-cooled condenser is being commissioned.  The control system designer has utilized a drybulb-following control strategy to reset the system saturated condensing temperature (SCT) setpoint. The refrigeration engineer has calculated that adding a TD of 11°F (6.1°C) above the ambient drybulb temperature should provide a saturated condensing temperature setpoint that minimizes the combined compressor and condenser fan power usage throughout the year.  What might the system SCT and SCT setpoint trends look like over an example day?

Answer

The following figure illustrates the actual saturated condensing temperature and SCT setpoints over an example day using the drybulb-following control strategy with an 11°F (6.1°C) TD and also observing the 70°F (21°C) minimum condensing temperature requirement.  As the figure shows, the SCT setpoint is continuously reset 11°F (6.1°C) above the ambient drybulb temperature, but is bounded by the minimum and maximum SCT setpoints.  The figure also shows a maximum SCT setpoint (in this example, 90°F (32.2°C) which may be utilized to limit the maximum control setpoint, regardless of the ambient temperature value or TD parameter.

Section 120.6(a)4F Condenser Specific Efficiency

Requirements for Design Condensing Temperatures relative to design ambient temperatures, as described above for §120.6(a)4A&B, help assure that there is enough condenser capacity to keeping condensing temperatures compressor head pressures at reasonable levels.  However the sizing requirements do not address condenser efficiency.  For example, rather than providing amply sized condenser surface area, a condenser selection could consist of a small condenser area using a large motor to blow a large amount of air through the heat exchanger surface to achieve the design condenser TD.  However, this would come at the expense of excessive fan motor horsepower.  Also, relatively high fan power consumption can result from using condenser fans that have poor fan efficiency or low fan motor efficiency.  Section 120.6(a)4F addresses these and other factors affecting condenser fan power by setting minimum specific efficiency requirements for condensers.

All newly installed indoor and outdoor evaporative condensers, and outdoor air-cooled condensers to be installed on new refrigeration systems shall meet the minimum specific efficiency requirements shown in Table 10-6.

Table 10-6 – Fan-powered Condensers – Minimum Specific Efficiency Requirements

CONDENSER TYPE

REFRIGERANT TYPE

MINIMUM SPECIFIC EFFICIENCY

RATING CONDITION

Outdoor Evaporative-Cooled with THR Capacity > 8,000 MBH

All

350 Btuh/Watt

100°F Saturated Condensing Temperature (SCT), 70°F Outdoor Wetbulb Temperature

Outdoor Evaporative-Cooled with THR Capacity < 8,000 MBH and Indoor Evaporative-Cooled

All

160 Btuh/Watt

Outdoor Air-Cooled

Ammonia

75 Btuh/Watt

105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature

Halocarbon

65 Btuh/Watt

Indoor Air-Cooled

All

Exempt

Condenser specific efficiency is defined as:

Condenser Specific Efficiency = Total Heat Rejection (THR) Capacity / Input Power

The total heat rejection capacity is at the rating conditions of 100°F Saturated Condensing Temperature (SCT) and 70°F outdoor wetbulb temperature for evaporative condensers, and 105°F SCT and 95°F outdoor drybulb temperature for air-cooled condensers.  Input power is the electric input power draw of the condenser fan motors (at full speed), plus the electric input power of the spray pumps for evaporative condensers.  The motor power is the manufacturer’s published applied power for the subject equipment, which is not necessarily equal to the motor nameplate rating.  Power input for secondary devices such as sump heaters shall not be included in the specific efficiency calculation.

As shown in Table 10-6 the Standards have different minimum efficiencies depending on the type of condenser that is being used.  The different classifications of condenser are:

•      Outdoor, evaporative, THR greater than 8,000 MBH at specific efficiency rating conditions

•      Outdoor, evaporative, THR less than 8,000 MBH at specific efficiency rating conditions

•      Indoor, evaporatively cooled

•      Outdoor, air-cooled, ammonia refrigerant

•      Outdoor, air-cooled, halocarbon refrigerant

•      Indoor, air-cooled

The data published in the condenser manufacturer’s published rating for capacity and power shall be used to calculate specific efficiency.  For evaporative condensers, manufacturers typically provide nominal condenser capacity, and tables of correction factors that are used to convert the nominal condenser capacity to the capacity at various applied condensing temperatures and wetbulb temperatures.  Usually the manufacturer publishes two sets of correction factors: one is a set of “heat rejection” capacity factors, while the others are “evaporator ton” capacity factors.  Only the “heat rejection” capacity factors shall be used to calculate the condenser capacity at the efficiency rating conditions for the purpose of determining compliance with this section.

For air-cooled condensers, manufacturers typically provide the capacity at a given temperature difference (TD) between SCT and drybulb temperature.  Manufacturers typically assume that air-cooled condenser capacity is linearly proportional to TD; the catalog capacity at 20°F TD is typically twice as much as at 10°F TD.  The condenser capacity for air-cooled condensers at a TD of 10°F shall be used to calculate efficiency.  If the capacity at 10°F TD is not provided, the capacity shall be scaled linearly.

Depending on the type of condenser, the actual manufacturer’s rated motor power may vary from motor nameplate in different ways.  Air cooled condensers with direct-drive OEM motors may use far greater input power than the nominal motor horsepower would indicate.  On the other hand, evaporative condenser fans may have a degree of safety factor to allow for higher motor load in cold weather conditions (vs. the 100°F SCT/70°F WBT specific efficiency rating conditions).  Thus, actual motor input power from the manufacturer must be used for direct-drive air-cooled condensers while for large (i.e. > 8,000 MBH) evaporative condensers and other belt drive condensers, the full load motor rating is generally conservative but manufacturer’s applied power should be used whenever possible to more accurately determine specific efficiency.

Example 10-48

Question

An evaporative condenser is being considered for use in an outdoor application on a new refrigerated warehouse.  The refrigerant is ammonia.  The condenser manufacturer’s catalog provides the following information:

For this example, model number D551 is being considered.  Elsewhere in the catalog, it states that condenser model D551 has two 7.5 HP fan motors and one 5 HP pump motor.  Fan motor efficiencies and motor loading factors are not provided.  Does this condenser meet the minimum efficiency requirements?

Answer

First, the condenser capacity must be calculated at the efficiency rating condition. From Table 10-4, we see that the rating conditions for an outdoor evaporative condenser are 100°F SCT, 70°F WBT.  From the Base Heat Rejection table above, we see the nominal capacity for model D551 is 5,513 MBH.  From the Heat Rejection Capacity Factors table, we see that the correction factor for 100°F SCT, 70°F WBT is 0.88.  The capacity of this model at specific efficiency rating conditions is 5,513 MBH / 0.88 = 6,264 MBH.  Since 6,264 MBH is less than 8,000 MBH, we can see from Table10-4that the minimum specific efficiency requirement is 160 (Btu/hr)/Watt.

To calculate input power, we will assume 100% fan and pump motor loading and minimum motor efficiency since the manufacturer has not yet published actual motor input power at the specific efficiency rating conditions.  We look up the minimum motor efficiency from Nonresidential Appendix NA3: Fan Motor Efficiencies.  For a 7.5 HP 4-pole open fan motor, the minimum efficiency is 91.0%.  For a 5 HP 6-pole open pump motor, the minimum efficiency is 89.5%.  The fan motor input power is calculated to be:

2 Motors x 7.5 HP/Motor x 746 Watts/HP x 100% assumed loading/ 91% Efficiency = 12.297 Watts

The pump motor input power is calculated to be:

1 Motors x 5 HP/Motor x 746 Watts/HP x 100% assumed loading/ 89.5% Efficiency = 4.168 Watts

The combined input power is therefore:

12.297 Watts + 4.168 Watts = 16.464 Watts

Note: Actual motor power should be used when available (see notes in text).

Finally, the efficiency of the condenser is:

(6,264 MBH x 1000 Btuh/MBH) / 16.464 Watts = 381 Btuh/Watt

381 Btu/hr per Watt is higher than the 160 Btu/hr per Watt requirement.  This condenser meets the minimum efficiency requirements.

Condenser Fin Spacing

According to Section 120.6(a)4G air-cooled condensers shall have a fin density no greater than 10 fins per inch.  Condensers with higher fin densities have a higher risk of fouling with airborne debris.  This requirement does not apply to air-cooled condensers that utilize a micro-channel heat exchange surface, since this type of surface is not as susceptible to permanent fouling in the same manner as traditional tube-and-fin condensers with dense fin spacing.

 

D.   Compressors

Compressors on new refrigeration systems must follow the design and control requirements as described in §120.6(a)5.

Minimum Condensing Temperature

Floating head control is one of the largest energy savings measures applied to refrigeration systems.  This control attempts to keep condensing temperatures as low as possible (while not consuming too much condenser fan energy) as this reduces compressor head pressure which directly impact compressor energy.  When ambient temperatures are low the primary constraint on how low the condensing temperature can be reset is the design requirements of the compressor and associated system components.

Section 120.6 (a)5A addresses the compatibility of the compressor design and components with the requirements for floating head control.  All compressors that discharge to the condenser(s) and all associated components (coalescing oil separators, expansion valves for liquid injection oil cooling, etc.) must be capable of operating at a condensing temperature of 70°F (21°C) or less.  Note that oil separator sizing is often governed by the minimum condensing temperature as well as other factors, such as the maximum suction temperature.  Suction temperatures above the design value may occur under floating suction temperature control schemes.

The system designer should also keep in mind that other design parameters such as piping run-lengths or evaporator defrost requirements must be considered to meet this requirement.

Screw Compressor Control at Part-Load

New open-drive screw compressors in new refrigeration systems with a design saturated suction temperature (SST) of 28°F or lower shall vary compressor speed as the primary means of capacity control.  The compressor speed shall reduce to the manufacturer-specified minimum speed before unloading via slide valve.  Similarly, when the load increases, the compressor shall increase to 100% slide valve before increasing speed.  This requirement applies only to compressors discharging to the condenser (i.e. single stage or the high stage of a two-stage system) and only to suction groups that consist of a single compressor.

An exception to §120.6(a)5 is provided for compressors on a refrigeration system with more than 20% of the design cooling load from quick chilling or freezing space, or non-space process refrigeration cooling.  The “refrigeration system” refers to the entire associated system, (i.e. the refrigerant charge) not the suction group.  While variable speed compressor control may be cost effective in many instances and may be considered by the system designer, this exception exists to allow for situations such as seasonal processes with low operating hours or loads that may be precisely matched to a fully loaded compressor.

New screw compressors with a motor nameplate power greater than 150HP shall incorporate the capability to automatically vary the volume ratio (i.e. variable Vi) in order to optimize efficiency at off-design operating conditions.

Example 10-49

Question

The system shown below has three 200 HP open-drive screw compressors serving three different suction levels and one 200 HP backup or swing open-drive screw compressor that can be connected by valve into any of the three suction lines.  Does this count as having more than one compressor per suction group and exempt the compressors from the requirements in §120.6(a)5B?

Answer

Probably not.  The Exception 1 to §120.6(a)5B only applies when a suction group has two or more dedicated compressors. A compressor that is used solely as backup does not count as a dedicated compressor.  As a result, all compressors (1, 2, 3, and 4) in the example above must comply with §120.6(a)5B and use variable speed control as the primary means of capacity control.

However, if Compressor 1 is actually required to meet the design load of one of the suction groups, it could be considered part of that suction group and variable speed control would not be required.  Whether a swing compressor is really a back-up compressor or part of a suction group should be apparent from the design loads and capacities 'listed in the design documents.

 

 

E.   Acceptance Requirements

The Standards have acceptance test requirements for:

1.   Electric underslab heating controls

2.   Evaporator fan motor controls

3.   Evaporative condensers

4.   Air-cooled condensers

5.   Variable speed compressors

These test requirements are described in Chapter 13 and the Reference Nonresidential Appendix NA7.10. They are described briefly in the following paragraphs.

Electric Underslab Heating Controls

Controls for underslab electric heating controls, when used for freeze protection on freezer floors, are tested to ensure heat is automatically turned off during summer on-peak electric periods.

Evaporator Fan Motor Controls

Evaporator equipment and controls are checked for proper operation. The controls are tested to ensure the fan speed automatically varies in response the temperature and/or humidity of the space.

Evaporative Condensers

Evaporative condensers and variable speed fan controls are checked to ensure the required minimum SCT setpoint of 70°F or lower is implemented, and the condenser fans continuously vary in unison to maintain a target temperature difference between the SCT and the wet bulb temperature. Trends of wet bulb temperature and SCT can be used to verify the controls over time.

The condenser control TD or offset is a key parameter in fine-tuning the operation of the fans and maximizing the energy savings.  In best practice, this control setting should be adjusted during average loaded so that the fan average 60-80% speed when in the control range (i.e. between the minimum and maximum SCT setpoints).

Air-cooled Condensers

Air-cooled condensers and variable speed fan controls are checked to ensure the required minimum SCT setpoint of 70°F or lower is implemented, and the condenser fans continuously vary in unison to maintain a target temperature difference between the SCT and dry bulb temperature.  Trends of dry bulb temperature and SCT can be used to verify the controls over time.

The condenser control TD is a key parameter in fine-tuning the operation of the fans and maximizing the energy savings.  This control setting should be adjusted during average loaded so that condenser capacity is effectively utilized but fan speed is not excessive.

Variable Speed Compressors

The controls and equipment for the variable speed control of screw compressors is checked and certified as part of the acceptance requirements.  The compressor should unload capacity by reducing speed to the minimum speed setpoint before unloading by slide valve or other means.  Control system trend screens can also be used to verify that the speed varies automatically in response to the load.

10.6.4  Additions and Alterations

A.   Requirements

Requirements related to refrigerated warehouse additions and alterations are covered by the Standards in §141.1(a).  The specific requirements for additions and alterations for commercial refrigeration are included in 120.6(a).  Definitions relevant to refrigerated warehouses include:

•      An addition is a change to an existing refrigerated warehouse that increases refrigerated floor area and volume.  Additions are treated like new construction.

•      When an unconditioned or conditioned building; or unconditioned or conditioned part of a building adds refrigeration equipment so that it becomes refrigerated, this area is treated as an addition.

•      An alteration is a change to an existing building that is not an addition or repair. An alteration could include installing new evaporators, a new lighting system, or a change to the building envelope, such as adding insulation.

•      A repair is the reconstruction or renewal of any part of an existing building or equipment for the purpose of its maintenance. For example, a repair could include the replacement of an existing evaporator or condenser.

Any addition or altered space must meet all applicable mandatory requirements.  Repairs must not increase the preexisting energy consumption of the repaired component, system, or equipment; otherwise, it is considered to be an alteration.

 

Example 10-50

Question

The new construction is an addition to an existing refrigerated warehouse. The new space is served by an existing refrigeration plant. Does the refrigeration plant need to be updated to meet the Standards?

Answer

No. The new construction must comply with the Standards; however, the existing refrigeration plant equipment is exempt from the Standards.

 

Example 10-51

Question

The new construction includes an addition to refrigerated space and expansion of the existing refrigeration plant. Is the existing refrigeration equipment subject to the Standards requirements?

Answer

No. Only the new equipment installed in the added refrigerated space and any new compressors added to the existing plant are subject to the requirements of the Standards. If a new refrigeration system was installed with a new condenser for the addition then the new condenser must also comply with the Standards.

 

Example 10-52

Question

An upgrade to an existing refrigerated storage space includes replacing all of the existing evaporators with new evaporators. Do the new evaporators need to comply with the Standards?

Answer

Yes. A complete renovation of the evaporators in the space is considered to be an alteration. The alteration requirements apply when all of the evaporators in the space are changed.

 

Example 10-53

Question

An existing refrigerated storage space is adding additional evaporators to meet an increase in the refrigeration load. Do the new evaporators need to comply with the Standards?

Answer

No. The alteration requirements apply only when all of the evaporators in the space are changed.

 

Example 10-54

Question

An existing evaporator is being replaced by a new evaporator as part of system maintenance. Does the new evaporator need to comply with the Standards?

Answer

No. Replacement of an evaporator during system maintenance is considered a repair. However, the energy consumption of the new evaporator must not exceed that of the equipment it replaced.

10.6.5  Compliance Documentation (NRCC-PRC-06-E through NRCC-PRC-08-E) for Refrigerated Warehouses

At the time a building permit application is submitted to the enforcement agency, the applicant also submits plans and energy compliance documentation. This section describes the forms and recommended procedures documenting compliance with the requirements of the Standards for refrigerated warehouses. The following discussion is addressed to the designer preparing construction documents and compliance documentation, and to the enforcement agency plan checkers who are examining those documents for compliance with the Standards.

A.   NRCC-PRC-06-E for Refrigerated Warehouses: Certificate of Compliance

NRCC-PRC-06-E is the primary form for Refrigerated Warehouses, which provides compliance information for the use of the enforcement agency’s field inspectors.  This form must be included on the plans, usually near the front of the assembly drawings. A copy of these forms should also be submitted to the enforcement agency along with the rest of the compliance submittal at the time of building permit application. With enforcement agency approval, the applicant may use alternative formats of these forms (rather than the Energy Commission’s forms), provided the information is the same and in similar format.

Project Description

PROJECT NAME is the title of the project, as shown on the plans and known to the enforcement agency.

CLIMATE ZONE is the California Climate zone in which the project is located.  See Reference Joint Appendix JA2 for a listing of climate zones.

CONDITIONED FLOOR AREA has a specific meaning under the Standards.  The number entered here should match the floor area entered on the other forms.

PROJECT ADDRESS is the address of the project as shown on the plans and known to the enforcement agency.

DATE is the last revision date of the plans.  If the plans are revised after this date, it may be necessary to re-submit the compliance documentation to reflect the altered design.  Note that it is the enforcement agency’s discretion whether or not to require new compliance documentation.

General Information

PHASE OF CONSTRUCTION indicates the status of the building project described in the compliance documents.  Refer to Section 1.7 for detailed discussion of the various choices.

NEW CONSTRUCTION should be checked for all new buildings, newly conditioned space or for new construction in existing buildings (tenant improvements, see Section 1.7.11, 1.7.12) that are submitted for envelope compliance.

ADDITION should be checked for an addition which is not treated as a stand-alone building, but which uses option 2 described in Section 1.7.14.  Tenant improvements that increase conditioned floor area and volume are additions.

ALTERATION should be checked for alterations to an existing building mechanical systems (see Section 1.7.13).  Tenant improvements are usually alterations.

Documentation Author’s Declaration Statement

The CERTIFICATE of COMPLIANCE is signed by both the Documentation Author and the Principal Refrigerated Warehouse Designer who is responsible for preparation of the plans of building.  This latter person is also responsible for the energy compliance documentation, even if the actual work is delegated to a different person acting as Documentation Author.  It is necessary that the compliance documentation be consistent with the plans.

DOCUMENTATION AUTHOR is the person who prepared the energy compliance documentation and who signs the Declaration Statement.  The person’s telephone number is given to facilitate response to any questions that arise.  A Documentation Author may have additional certifications such as an Energy Analyst or a Certified Energy Plans Examiner certification number.  Enter number in the EA# or CEPE# box.

Principal Refrigerated Warehouse Designer’s Declaration Statement

The Declaration Statement is signed by the person responsible for preparation of the plans for the building.  This principal designer is also responsible for the energy compliance documentation, even if the actual work is delegated to someone else (the Documentation Author as described above).  It is necessary that the compliance documentation be consistent with the plans.  The Business and Professions Code governs who is qualified to prepare plans and therefore to sign this statement.  See Section 2.2.2 Permit Application for applicable text from the Business and Professions Code.

Mandatory Measures Note Block

The person with overall responsibility must ensure that the Mandatory Measures that apply to the project are 'listed on the plans.  The format of the list is left to the discretion of the Principal Refrigerated Warehouse Designer.

Insulation Requirements (§120.6(a)1)

□    Exterior surfaces shall be insulated at least to the R-values of Table 120.6-A

Underslab Heating (§120.6(a)2)

□     Electric resistance heat shall not be used for the purposes of underslab heating.

Evaporators (§120.6(a)3)

□     Single phase fan motors less than 1 hp and less than 460 Volts in newly installed evaporators shall be electronically commutated motors or shall have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating conditions.

□     Evaporator fans served either by a suction group with multiple compressors, or by a single compressor with variable capacity capability shall be variable speed and the speed shall be controlled in response to space temperature or humidity.

□     Evaporator fans served by a single compressor that does not have variable capacity shall utilize controls to reduce airflow by at least 40 percent for at least 75 percent of the time when the compressor is not running.

Condensers (§120.6(a)4)

□     Design saturated condensing temperature for evaporative-cooled condensers and water-cooled condensers served by fluid coolers or cooling towers shall be less than or equal to:

§ Design wb +20oF in locations where the design wb temperature is ≤ 76oF or

§ Design wb +19oF in locations where the design wb temperature is between 76oF and 78oF or

§ Design wb +18oF in locations where the design wb temperature is ≥ 78oF or

□     The increase in hydrofluorocarbon (HFC) refrigerant charge associated with refrigeration heat recovery equipment and piping shall be no greater than 0.35 lbs. per 1,000 Btu/h of heat recovery heating capacity.

□     Design saturated condensing temperatures for air-cooled condensers shall be less than or equal to the design db temperature +10oF for systems serving freezers and shall be ≤ the design db temperature +15oF for systems serving coolers.

□     All condenser fans for evaporative-cooled condensers or fans on cooling towers or fluid coolers shall be continuously variable speed and the condensing temperature control system shall control the speed of all fans serving a common condenser high side in unison.  The minimum condensing temperature setpoint shall be ≤ 70oF.

□     All condenser fans for air-cooled condensers shall be continuously variable speed and the condensing temperature or pressure control system shall control the speed of all condenser fans serving a common condenser high side in unison.  The minimum condensing temperature setpoint shall be ≤ 70oF.

□     Condensing temperature reset.  The condensing temperature setpoint of systems served by air-cooled condensers shall be reset in response to ambient db temperature.  The condensing temperature setpoint of systems served by evaporative-cooled condensers or water-cooled condensers shall be reset in response to ambient wb temperatures.

□     Fan-powered condensers shall meet the condenser efficiency requirements 'listed in Table 120.6-B

□     Air-cooled condensers shall have a fin density no greater than 10 fins per inch.

Compressors (§120.6(a)5)

□     Compressors shall be designed to operate at a minimum condensing temperature of 70oF or less.

□     Open-drive screw compressors in new refrigeration systems with a design saturated suction temperature (SST) of 28oF or lower that discharges to the system condenser pressure shall control compressor speed in response to the refrigeration load.

□     Screw compressors with nominal electric motor power greater than 150 HP shall include the ability to automatically vary the compressor volume ratio (Vi) in response to operating pressures.

Infiltration Barriers (§120.6(a)6)

□     Passageways between freezers and higher-temperature spaces, and passageways between coolers and non-refrigerated spaces, shall have an infiltration barrier consisting of strip curtains, an automatically-closing door, or an air curtain designed by the manufacturer for use in the passageway and temperature for which it is applied.

Refrigeration System Acceptance (§120.6(a)7)

□     Electric resistance underslab heating systems shall be tested in accordance with NA 7.10.1.

□     Evaporator fan motor controls shall be tested in accordance with NA 7.10.2.

□     Evaporative condensers shall be tested in accordance with NA 7.10.3.1.

□     Air-cooled condensers shall be tested in accordance with NA 7.10.3.2.

□     Variable speed compressors shall be tested in accordance with NA 7.10.4.

 

Refrigerated Warehouse Compliance Forms and Worksheets Block

Principle Refrigerated Warehouse Designer should indicate the compliance forms and worksheets that are applicable to the project.

Required Acceptance Tests

This form is new to the set of compliance forms for Refrigerated Warehouses.

PROJECT NAME is the title of the project, as shown on the plans and known to the enforcement agency.

DATE is the last revision date of the plans.  If the plans are revised after this date, it may be necessary to re-submit the compliance documentation to reflect the altered design.  Note that it is the enforcement agency‘s discretion whether or not to require new compliance documentation.

The form includes a fill-in-the-blank table to indicate which acceptance tests apply to the project.  Acceptance tests for Refrigerated Warehouses are described in Nonresidential Appendix NA7 and are 'listed in Table 10-7 below.

 

Table10-7 - Acceptance Tests for Refrigerated Warehouses

Test per Section NA7

Applicable Equipment or System

NA7.10.1

Electric resistance underslab heating system

NA7.10.2

Evaporator fan motor controls

NA7.10.3.1

Evaporative condensers

NA7.10.3.2

Air-cooled condensers

NA7.10.4

Variable speed compressors

The Principle Refrigerated Warehouse Designer should list the equipment and systems that require acceptance tests and check the boxes next to the acceptance tests that apply to the respective equipment and systems.  The Enforcement Agency should not accept the form unless the correct boxes are checked and/or filled in and the form is signed by the persons performing the tests.

NRCC-PRC-06-E for Refrigerated Warehouses: Condenser Specific Efficiency Worksheet            

Page 1 of 3

Evaporative Condensers

This page includes the specific efficiency calculations for evaporative condensers.  Fluid coolers are exempt from the specific efficiency requirements.

TAG/ID indicates the identification name of the condenser that matches the building plans.

FANS – MOTOR POWER (HP) indicates the fan motor power in HP on the name plate of the fan motor.

FANS – MOTOR EFFICIENCY indicates the fan motor efficiency on the name plate of the fan motor.

FANS – MOTOR POWER INPUT (KW) indicates the fan motor input power in kW calculated by using FANS – MOTOR POWER (HP) and FANS – MOTOR EFFICIENCY.

FANS – TOTAL FAN POWER (KW) indicates the sum of the fan motor power inputs of all fans of the condenser in kW.

PUMPS – MOTOR POWER (HP) indicates the pump motor power in HP on the name plate of the pump motor.

PUMPS – MOTOR EFFICIENCY indicates the pump motor efficiency on the name plate of the pump motor.

PUMPS – MOTOR POWER INPUT (KW) indicates the pump motor input power in kW calculated by using PUMPS – MOTOR POWER (HP) and PUMPS – MOTOR EFFICIENCY.

PUMPS – TOTAL FAN POWER (KW) indicates the sum of the total pump motor input powers of all pumps of the condenser in kW.

CONDENSER - CAPACITY (MBH) indicates the condenser heat rejection capacity from the manufacturer’s catalog at 100ºF saturated condensing temperature and 70ºF ambient wetbulb temperature.

CONDENSER - TOTAL INPUT POWER (KW) indicates the sum of the input powers of all fans and pumps of the condenser in kW.

CONDENSER – SPECIFIC EFFICIENCY (BTUH/WATT) indicates the specific efficiency of the condenser calculated from CONDENSER - CAPACITY (MBH) and CONDENSER - TOTAL INPUT POWER (KW).

Page 2 of 3

Air-cooled condensers

This page includes the specific efficiency calculations for air-cooled condensers.

TAG/ID indicates the identification name of the condenser that matches the building plans.

NUMBER OF FANS indicates the number of fans on the condenser.

MOTOR POWER (HP) indicates the fan motor power in HP on the name plate of the fan motor.

MOTOR EFFICIENCY indicates the fan motor efficiency on the name plate of the fan motor.

TOTAL INPUT POWER (KW) indicates the sum of the input powers of all fans of the condenser in kW.  It is calculated by using NUMBER OF FANS, MOTOR POWER (HP) and MOTOR EFFICIENCY.

CONDENSER - CAPACITY (MBH) indicates the condenser heat rejection capacity from the manufacturer’s catalog at 105ºF saturated condensing temperature and 95ºF ambient drybulb temperature (10ºF TD).

CONDENSER – SPECIFIC EFFICIENCY (BTUH/WATT) indicates the specific efficiency of the condenser calculated from CONDENSER - CAPACITY (MBH) and TOTAL INPUT POWER (KW).

NRCC-PRC-07-E for Refrigerated Warehouses: Refrigerated Warehouse Space Requirements            

Page 1 of 3

Page 1 of 3 includes Insulation Details.

PROJECT NAME is the title of the project, as shown on the plans and known to the enforcement agency.

DATE is the last revision date of the plans.  If the plans are revised after this date, it may be necessary to re-submit the compliance documentation to reflect the altered design.  Note that it is the enforcement agency‘s discretion whether or not to require new compliance documentation.

BUILDING TYPE indicates the area of the warehouse.  If the Refrigerated Warehouse space is less than 3,000 square feet then does not have to comply with the space requirements of the Standards.  However, it must meet the requirements of the Appliance Efficiency Regulations for walk-in coolers or freezers contained in the Appliance Efficiency Regulations (California Code of Regulations, Title 20, Sections 1601 through 1608).

TAG/ID indicates the identification name that matches the building plans.

SPACE indicates the area type, either cooler (design temperature greater than or equal to 28oF, but less than 55oF) or freezer (less than 28oF).

PRODUCTIVE UNDERSLAB HEATING indicates whether underslab heating is provided in such a way that produces productive refrigeration capacity for an associated refrigeration system. 

ASSEMBLY TYPE indicates whether the assembly is a wall, roof, ceiling or floor.

INSTALLED INSULATION R-VALUE is the actual installed R-value of insulation as shown on the referenced assembly drawings of the plans.

MINIMUM REQUIRED INSULATION R-VALUE     is the minimum insulation R-value specified in Table 120.6-A of the Standards.

ASSEMBLY COMPLIANCE is determined by comparing the installed R-value versus the minimum required R-value and should be indicated in the Pass/Fail checkboxes provided.

Page 2 of 3

Page 2 of 3 includes mandatory requirements for underslab heating and evaporators.  As stated on the page, the required information should be either 'listed on the form or the page from the plans or specifications section and the paragraph displaying the required information should be indicated on the form.

Page 3 of 3

Page 3 of 3 includes Infiltration Barrier Details

PROJECT NAME is the title of the project, as shown on the plans and known to the enforcement agency.

DATE is the last revision date of the plans.  If the plans are revised after this date, it may be necessary to re-submit the compliance documentation to reflect the altered design.  Note that it is the enforcement agency‘s discretion whether or not to require new compliance documentation.

BARRIER NAME indicates the name of the infiltration barrier that matches the building plans.

AREA indicates the area of the opening filled by the infiltration barrier.

EXEMPT indicates whether the opening is exempt from having an infiltration barrier.

BARRIER TYPE indicates whether the barrier is a strip curtain, an automatically-closing door, or an air curtain.

PASS/FAIL – The barrier passes If it is exempt or if it complies with section 120.6(a)6. Otherwise, it fails

NRCC-PRC-08-E for Refrigerated Warehouses: Refrigerated Warehouse System Requirements            

This form includes mandatory requirements for condensers and compressors.  As stated on the form, the required information should be either 'listed on the form or the page from the plans or specifications section and the paragraph displaying the required information should be indicated on the form.

Documentation Author’s Declaration Statement

The CERTIFICATE of COMPLIANCE is signed by both the Documentation Author and the Principal Refrigerated Warehouse Designer who is responsible for preparation of the plans of building.  This latter person is also responsible for certifying all the mandatory requirements for the condensers and compressors are met as 'listed in the previous pages of this form, even if the actual work is delegated to a different person acting as Documentation Author. It is necessary that the compliance documentation be consistent with the plans.

DOCUMENTATION AUTHOR is the person who prepared this compliance documentation and who signs the Declaration Statement.  The person’s telephone number is given to facilitate response to any questions that arise.  A Documentation Author may have additional certifications such as an Energy Analyst or a Certified Energy Plans Examiner certification number.  Enter number in the EA# or CEPE# box.

Principal Refrigerated Warehouse Designer’s Declaration Statement

The Declaration Statement is signed by the person responsible for preparation of the plans for the building.  This principal designer is also responsible for the compliance documentation, even if the actual work is delegated to someone else (the Documentation Author as described above).  It is necessary that the compliance documentation be consistent with the plans.  The Business and Professions Code governs who is qualified to prepare plans and therefore to sign this statement.  See Section 2.2.2 Permit Application for applicable text from the Business and Professions Code.